Worked example
Example: Overnight 14 h standing loss: 300 L tank at 60 C, UA 2 W/K, 15 C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Mass of water in the tank | 300.00 kg |
| Specific heat | 4.1800 kJ/(kg·K) |
| Tank loss coefficient-area product | 0.002000 kW/K |
| Temperature around the tank | 15.000 °C |
| Tank temperature at the start | 60.000 °C |
| Solar energy added during the period | 0 MJ |
| Energy removed to the load during the period | 0 MJ |
| Period | 14.000 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Tank loss during the period (Euler) | 4.5360 MJ |
| Final temperature, one Euler step | 56.383 °C |
| Final temperature, exact for steady rates | 56.524 °C |
| Temperature the tank would settle at | 15.000 °C |
| Tank time constant M c_p/(UA) | 174.17 h |
Open this example in the calculator and change any input.
Formula
\(T_s^+ = T_s + \frac{\Delta t}{(Mc_p)_s}\left[Q_u - L_s - (UA)_s(T_s - T'_a)\right]\)
\(T_s(\Delta t) = T_\infty + (T_s - T_\infty)e^{-\Delta t(UA)_s/(Mc_p)_s}, \quad T_\infty = T'_a + \frac{(Q_u - L_s)/\Delta t}{(UA)_s}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(M\) | Mass of water in the tank | kg |
| \(c_p\) | Specific heat | J/(kg·K) |
| \((UA)_s\) | Tank loss coefficient-area product | W/K |
| \(T'_a\) | Temperature around the tank | K |
| \(T_s\) | Tank temperature at the start | K |
| \(Q_u\) | Solar energy added during the period | J |
| \(L_s\) | Energy removed to the load during the period | J |
| \(\Delta t\) | Period | s |
| \(Q_{loss}\) | Tank loss during the period (Euler) | J |
| \(T_s^+\) | Final temperature, one Euler step | K |
| \(T_s(\Delta t)\) | Final temperature, exact for steady rates | K |
| \(T_\infty\) | Temperature the tank would settle at | K |
| \(\tau\) | Tank time constant M c_p/(UA) | s |
Method and standards
Energy balance of a fully mixed (unstratified) storage tank.
Where it is used
- Hour-by-hour solar system simulation by hand.
- Overnight temperature drop of a hot-water store.
Common mistakes
- Mixing energy over the period with power.
- Using a long step that overshoots the surrounding temperature.
Assumptions and limits
- Fully mixed; constant gain and load rates over the period for the exact solution.
Questions and answers
When is one Euler step enough?
When the period is short compared with the tank time constant M c_p/(UA), usually days for a well-insulated tank; the exact solution is shown for comparison.
How much storage is usual?
50 to 100 litres of water per m² of collector for space and water heating; the f-chart assumes 75 L/m².
What do the defaults represent?
An illustrative case: Overnight 14 h standing loss: 300 L tank at 60 C, UA 2 W/K, 15 C. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Duffie and Beckman, Solar Engineering of Thermal Processes, 4th ed. (Wiley, 2013), sec. 8.3, eq. 8.3.3 and Example 8.3.1