Worked example
Example: Illustrative: 30 % shaded at 180 W/m2, rest at 950 W/m2, 0.010 kg/(m2 s), 45 C inlet. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Share of area in zone 1 (entered first by the flow) | 30.000 % |
| Radiation on zone 1 | 180.00 W/m² |
| Radiation on zone 2 | 950.00 W/m² |
| Transmittance–absorptance product, zone 1 | 75.000 % |
| Transmittance–absorptance product, zone 2 | 85.000 % |
| Heat removal factor | 95.000 % |
| Heat removal factor times loss coefficient | 5.0000 W/(m²·K) |
| Flow per unit collector area | 36.000 kg/(m²·h) |
| Fluid specific heat | 4.1900 kJ/(kg·K) |
| Inlet temperature | 45.000 °C |
| Ambient temperature | 15.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Zone coupling factor A_2F_RU_L/(ṁc_p) | 0.083532 |
| Useful gain per unit area, flow as entered | 426.01 W/m² |
| Useful gain per unit area with the flow reversed | 410.00 W/m² |
| Gain using the area-average radiation | 425.46 W/m² |
| Temperature leaving zone 1 | 44.844 °C |
| Collector outlet temperature | 55.167 °C |
Open this example in the calculator and change any input.
Formula
\(Q_u = A_1F_R(\tau\alpha)_1(1 - K)G_{T,1} + A_2F_R(\tau\alpha)_2G_{T,2} - F_RU_L[A_1(1 - K) + A_2](T_i - T_a)\)
\(K = \frac{A_2F_RU_L}{\dot mc_p}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A_1/A\) | Share of area in zone 1 (entered first by the flow) | - |
| \(G_{T,1}\) | Radiation on zone 1 | W/m² |
| \(G_{T,2}\) | Radiation on zone 2 | W/m² |
| \((\tau\alpha)_1\) | Transmittance–absorptance product, zone 1 | - |
| \((\tau\alpha)_2\) | Transmittance–absorptance product, zone 2 | - |
| \(F_R\) | Heat removal factor | - |
| \(F_RU_L\) | Heat removal factor times loss coefficient | W/(m²·K) |
| \(\dot m/A\) | Flow per unit collector area | kg/(m²·s) |
| \(c_p\) | Fluid specific heat | J/(kg·K) |
| \(T_i\) | Inlet temperature | K |
| \(T_a\) | Ambient temperature | K |
| \(K\) | Zone coupling factor A_2F_RU_L/(ṁc_p) | - |
| \(Q_u/A\) | Useful gain per unit area, flow as entered | W/m² |
| \(Q_u/A\ (reversed)\) | Useful gain per unit area with the flow reversed | W/m² |
| \(Q_u/A\ (average)\) | Gain using the area-average radiation | W/m² |
| \(T_{o,1}\) | Temperature leaving zone 1 | K |
| \(T_o\) | Collector outlet temperature | K |
Method and standards
Series zones of one collector at different irradiance.
Where it is used
- Arrays with row-to-row shading.
- Collectors with planar reflectors.
Common mistakes
- Using the inlet temperature for both zones.
- Ignoring the shaded zone's lower (τα) for diffuse radiation.
Assumptions and limits
- Same F_R and U_L for both zones; steady state.
References
- Hottel–Whillier gain of two collector zones in series
Questions and answers
Does flow direction matter?
A little: sending the flow through the brightly lit zone last usually gains a few per cent, because the low-irradiance zone then works at the colder inlet.
Can I just average the radiation?
Usually yes; the average-radiation estimate is shown for comparison.
What do the defaults represent?
An illustrative row-shaded collector: 30 % of the area in shade at 180 W/m² and the rest at 950 W/m², F_R 0.95, F_RU_L 5.0 W/(m²·K), 0.010 kg/(m²·s) of water at 45 °C with 15 °C ambient.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Duffie and Beckman, Solar Engineering of Thermal Processes, 4th ed. (Wiley, 2013), sec. 10.6, eqs. 10.6.1 to 10.6.5 and Example 10.6.1