Worked example
Example: DN100 steam line at 180 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pipe outer diameter | 114.30 mm |
| Bare length | 40.000 m |
| Fluid temperature | 180.00 °C |
| Ambient temperature | 30.000 °C |
| Insulation thickness to apply | 50.000 mm |
| Insulation conductivity | 0.045000 W/(m·K) |
| Bare pipe emissivity | 90.000 % |
| Cladding emissivity | 10.000 % |
| Hours per year | 8,000.0 h |
| Boiler efficiency (same CV basis as the fuel cost) | 85.000 % |
| Fuel cost per GJ of fuel energy (same CV basis as η) | 600.00 - |
| Insulation cost per metre | 2,500.0 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Bare loss per metre | 1,023.2 W/m |
| Insulated loss per metre | 58.822 W/m |
| Fuel energy saved per year | 1,307.0 GJ |
| Cost saved per year | 784,195 |
| Payback (months) | 1.5302 |
Open this example in the calculator and change any input.
Formula
\(q' = \frac{T_i - T_a}{\dfrac{\ln(D/D_o)}{2\pi\lambda} + \dfrac{1}{h_{se}\pi D}}, \quad h_{se} = h_{cv} + h_r\ \ (\text{ISO 12241; bare pipe: } D = D_o,\ \text{no insulation term})\) \(\Delta E = \frac{(q'_b - q'_i)L\,t}{\eta}, \quad \Delta C = \Delta E\,c_f, \quad t_{pb} = \frac{12\,C_i L}{\Delta C}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D_o\) | Pipe outer diameter | m |
| \(L\) | Bare length | m |
| \(T_i\) | Fluid temperature | K |
| \(T_a\) | Ambient temperature | K |
| \(s\) | Insulation thickness to apply | m |
| \(\lambda\) | Insulation conductivity | W/(m·K) |
| \(\varepsilon_b\) | Bare pipe emissivity | - |
| \(\varepsilon_i\) | Cladding emissivity | - |
| \(t\) | Hours per year | s |
| \(\eta\) | Boiler efficiency (same CV basis as the fuel cost) | - |
| \(c_f\) | Fuel cost per GJ of fuel energy (same CV basis as η) | - |
| \(C_i\) | Insulation cost per metre | - |
| \(q'_b\) | Bare loss per metre | W/m |
| \(q'_i\) | Insulated loss per metre | W/m |
| \(\Delta E\) | Fuel energy saved per year | J |
| \(\Delta C\) | Cost saved per year | - |
| \(t_{pb}\) | Payback (months) | - |
Method and standards
ISO 12241 difference.
Where it is used
- Steam and condensate line audits.
- Maintenance prioritisation.
Common mistakes
- Ignoring wind outdoors.
- Wrong cladding emissivity.
Assumptions and limits
- Still air, steady state.
- The bare pipe surface is taken at the fluid temperature (inner film and wall neglected): right for steam, but for slow-moving liquids it overstates the bare loss and so the saving.
- Boiler efficiency and fuel cost per GJ on one calorific-value basis.
References
- ISO 12241 insulated and bare pipe heat loss (engine InsulatedPipe); fuel = heat/η
Questions and answers
40 m of bare DN100 steam pipe at 180 °C?
About 1.0 kW/m bare against 0.06 kW/m insulated: about 1,300 GJ of fuel a year and payback in about 1.5 months.
Valves and flanges?
A bare valve loses about as much as a metre or more of bare pipe; use insulating jackets.
Wind?
Raises bare losses well above the still-air value.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.