FireCADCalc

Heat Pump vs Fuel Boiler: Cost of Useful Heat

Annual running cost of a heat pump against a fuel-fired boiler for the same useful heat, from COP, electricity price, boiler efficiency and fuel price and CV.

Process steam and utilitiesFood, dairy and textile

Inputs

Examples: Diesel boiler vs heat pumpGas boiler vs heat pump

Results

Heat pumps suit low-temperature heat (below about 80 °C); COP falls as the delivery temperature rises.

Heat pump cost per year3,214,286
Boiler cost per year4,166,667
Saving with the heat pump952,381
Break-even COP2.1600

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Diesel boiler vs heat pump. The inputs, in the units selected above:

InputValue
Useful heat per year2,000.0 MWh
Heat pump seasonal COP3.2000 -
Electricity price per kWh8.0000 -
Boiler efficiency (same CV basis as CV)88.000 %
Fuel price per kg65.000 -
Fuel calorific value42.000 MJ/kg

Applying the formula below gives:

ResultValue
Heat pump cost per year5,000,000
Boiler cost per year1.2662e+07
Saving with the heat pump7,662,338
Break-even COP1.2636

Open this example in the calculator and change any input.

Formula

\(C_{HP} = \frac{Q}{3.6\times10^6\,COP}c_e, \quad C_B = \frac{Q}{\eta CV}p_f, \quad COP_{be} = \frac{c_e\,\eta\,CV}{3.6\times10^6\,p_f}\) (Q in J, CV in J/kg, c_e per kWh, p_f per kg)

Variables

Symbol Meaning SI unit
\(Q\) Useful heat per year J
\(COP\) Heat pump seasonal COP -
\(c_e\) Electricity price per kWh -
\(\eta\) Boiler efficiency (same CV basis as CV) -
\(p_f\) Fuel price per kg -
\(CV\) Fuel calorific value J/kg
\(C_{HP}\) Heat pump cost per year -
\(C_B\) Boiler cost per year -
\(\Delta C\) Saving with the heat pump -
\(COP_{be}\) Break-even COP -

Method and standards

Running cost.

Where it is used

  • Hot water and process heating decisions.
  • Decarbonisation options.

Common mistakes

  • Rated instead of seasonal COP.
  • GCV vs NCV efficiency.

Assumptions and limits

  • Same useful heat.
  • Boiler efficiency and CV on one basis (both GCV or both NCV).

References

  • Cost = Q/COP × electricity price vs Q/(η CV) × fuel price

Questions and answers

2000 MWh of heat, COP 3.2 at 8/kWh vs diesel at 65/kg, 88 %?

Heat pump 5,000,000, boiler 12,662,338 a year.

Break-even COP?

The COP at which both cost the same.

Process heat?

Good for washing, preheating and drying air below about 80 °C.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.