Worked example
Example: 800 kW, 0.82 to 0.97. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Maximum demand (active) | 800.00 kW |
| Present power factor | 82.000 % |
| Target power factor | 97.000 % |
| Demand charge per kVA per month | 350.00 - |
| Capacitor bank cost per kvar | 1,200.0 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Present kVA demand | 975.61 kVA |
| kVA demand at the target | 824.74 kVA |
| Capacitor needed | 357.90 kvar |
| Demand charge saved per year | 633,643 |
| Payback (months) | 8.1336 |
Open this example in the calculator and change any input.
Formula
\(S = \frac{P}{\cos\varphi}, \quad Q_c = P(\tan\varphi_1 - \tan\varphi_2), \quad \Delta C = 12(S_1 - S_2)c_d\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | Maximum demand (active) | W |
| \(\cos\varphi_1\) | Present power factor | - |
| \(\cos\varphi_2\) | Target power factor | - |
| \(c_d\) | Demand charge per kVA per month | - |
| \(c_c\) | Capacitor bank cost per kvar | - |
| \(S_1\) | Present kVA demand | VA |
| \(S_2\) | kVA demand at the target | VA |
| \(Q_c\) | Capacitor needed | var |
| \(\Delta C\) | Demand charge saved per year | - |
| \(t_{pb}\) | Payback (months) | - |
Method and standards
Power triangle.
Where it is used
- Electricity bill reduction.
- Energy audits.
Common mistakes
- Average instead of maximum demand.
- Ignoring harmonics.
Assumptions and limits
- Same active demand.
References
- S = P/cos φ; Q_c = P(tan φ₁ − tan φ₂)
Questions and answers
800 kW from 0.82 to 0.97 at 350 per kVA a month?
Demand falls from 976 to 825 kVA: about 633,643 a year.
Capacitor size?
About 358 kvar.
Harmonics?
With VFDs present, use detuned capacitor banks.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.