VFD Output: Speed, Voltage and Torque at a Frequency

Motor synchronous speed and V/f voltage at a variable frequency drive setting, with the torque and power available below and above base speed.

Thermal power plantProcess steam and utilities

Inputs

Examples: 4-pole 415 V 50 Hz motor at 35 HzSame motor at 60 Hz (field weakening)6-pole 460 V 60 Hz motor at 20 Hz

Results

Above base speed: field weakening, constant power, torque falls as 1/f.

Synchronous speed at that frequency1,800.0rpm
Output voltage (constant V/f up to rated)415.00V
Volts per hertz8.3000
Torque available83.333%
Power available100.00%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 4-pole 415 V 50 Hz motor at 35 Hz. The inputs, in the units selected above:

InputValue
Rated frequency of the motor50.000 Hz
Rated voltage of the motor415.00 V
Number of poles4.0000 -
Drive output frequency35.000 Hz

Applying the formula below gives:

ResultValue
Synchronous speed at that frequency1,050.0 rpm
Output voltage (constant V/f up to rated)290.50 V
Volts per hertz8.3000
Torque available100.00 %
Power available70.000 %

Open this example in the calculator and change any input.

Formula

\(N_s = \frac{2 f}{p}\ [\text{rev/s}] = \frac{120 f}{p}\ [\text{rpm}], \quad V = V_r \min\left(1, \frac{f}{f_r}\right), \quad \frac{V}{f} = \frac{V_r}{f_r}\)

\(\frac{T}{T_r} = 1\ (f \le f_r),\ \frac{f_r}{f}\ (f > f_r), \qquad \frac{P}{P_r} = \min\left(1, \frac{f}{f_r}\right)\)

Variables

Symbol Meaning SI unit
\(f_r\) Rated frequency of the motor 1/s
\(V_r\) Rated voltage of the motor V
\(p\) Number of poles -
\(f\) Drive output frequency 1/s
\(N_s\) Synchronous speed at that frequency 1/s
\(V\) Output voltage (constant V/f up to rated) V
\(V/f\) Volts per hertz -
\(T/T_r\) Torque available -
\(P/P_r\) Power available -

Method and standards

Synchronous speed and constant flux control.

Where it is used

  • Setting drive frequencies.
  • Checking motor capability at speed.

Common mistakes

  • Expecting rated torque above base speed.
  • Ignoring cooling at low speed.

Assumptions and limits

  • Constant torque (T/T_r = 1) below base frequency assumes the motor is cooled independently of speed. A self-cooled (shaft-fan) motor must be derated at low speed per its maker's curve; that derating is not applied. Above base frequency the voltage stays at V_r and the motor runs at constant power.

  • Linear V/f, no boost.

References

  • N_s = 120 f / p; constant V/f control (textbook)

Questions and answers

What speed does a 4-pole motor run at 35 Hz?

Synchronous 1050 rpm (less slip), at 290.5 V on a 415 V, 50 Hz motor.

What is the V/f ratio?

8.3 V/Hz for 415 V at 50 Hz; keeping it constant keeps the flux constant.

What happens above 50 Hz?

Voltage cannot rise, so flux and torque fall: constant power.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.