VFD Energy Saving (Fan or Pump)

Power and energy saved by a variable frequency drive instead of a damper, vanes or a throttling valve on a fan or pump, on a system curve with static head.

Thermal power plantProcess steam and utilitiesHydraulic Institute (pumps)PumpFan and blowerElectric motor

Inputs

Examples: ID fan 150 kW at 75 % flow, all friction, damper 85 %BFW pump 200 kW at 80 % flow, static 60 %, valve 92 %FD fan 75 kW at 60 % flow, inlet vanes 70 %

0 for an all-friction system (most ID and FD fans); a boiler feed pump working against drum pressure has a large static share.
Read it from the fan or pump curve at the reduced flow at full speed (with inlet vanes, from the maker's vane curves).

Results

Electrical power saved65.539kW
Energy saved per year524.31MWh
Cost saved per year (your currency)4,194,466
Electrical input with damper or valve134.21kW
Electrical input with VFD68.672kW
Shaft power with VFD63.281kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: ID fan 150 kW at 75 % flow, all friction, damper 85 %. The inputs, in the units selected above:

InputValue
Shaft power at the design duty (100 % flow)150.00 kW
Operating flow as a share of design75.000 %
Static share of the design pressure or head0 %
Shaft power with the damper or valve at this flow, as a share of P_d85.000 %
Drive (VFD) efficiency97.000 %
Motor efficiency95.000 %
Hours per year at this flow8,000.0 h
Electricity price per kWh (your currency)8.0000 -

Applying the formula below gives:

ResultValue
Electrical power saved65.539 kW
Energy saved per year524.31 MWh
Cost saved per year (your currency)4,194,466
Electrical input with damper or valve134.21 kW
Electrical input with VFD68.672 kW
Shaft power with VFD63.281 kW

Open this example in the calculator and change any input.

Formula

\(P_v = P_d\,f\left(s + (1-s)f^2\right) \qquad P_{e,v} = \frac{P_v}{\eta_m\,\eta_v} \qquad P_{e,t} = \frac{r_t\,P_d}{\eta_m}\)

\(\Delta P = P_{e,t} - P_{e,v} \qquad \Delta E = \Delta P\,t_{op} \qquad \Delta C = \Delta E\,[\text{kWh}]\cdot c_e\)

Variables

Symbol Meaning SI unit
\(P_d\) shaft power at the design duty W
\(f\) operating flow as a share of design –
\(s\) static share of the design pressure or head –
\(r_t\) throttled shaft power as a share of \(P_d\) –
\(\eta_v\) drive efficiency –
\(\eta_m\) motor efficiency –
\(t_{op}\) hours per year at this flow s
\(c_e\) electricity price per kWh –
\(\Delta P\) electrical power saved W
\(\Delta E\) energy saved per year J
\(\Delta C\) cost saved per year –
\(P_{e,t}\) electrical input with damper or valve W
\(P_{e,v}\) electrical input with VFD W
\(P_v\) shaft power with VFD W

Method and standards

With speed control the machine follows the system curve \(p = p_d(s + (1-s)f^2)\); at constant machine efficiency the shaft power is proportional to flow times pressure (the affinity laws of AMCA 99 and ANSI/HI 1.3 when \(s = 0\)). The throttled power comes from the machine's own curve at full speed.

Where it is used

  • Justifying variable speed drives on pumps and fans.
  • Energy audits of throttled systems.
  • Comparing damper and speed control.

Common mistakes

  • Using the cube law where static head is large.
  • Ignoring drive losses.
  • Assuming full-load hours when the load varies.

Assumptions and limits

  • Machine efficiency taken as constant at reduced speed: exact for \(s = 0\), optimistic when the static share is large.
  • Motor efficiency taken as equal in both cases; at low load it falls, which slightly favours the VFD.
  • One operating point; for a load profile add the savings of each point weighted by its hours.

References

  • Fan and pump affinity laws (AMCA 99, ANSI/HI 1.3)

Questions and answers

How much does a VFD save on a fan?

On an all-friction system the shaft power falls with the cube of flow. An ID fan of 150 kW running at 75 % flow needs 63 kW with a VFD against about 128 kW with its damper, saving 66 kW of electricity.

Why is the saving smaller on a feed pump?

A boiler feed pump must always reach drum pressure, so most of its head is static and does not fall with speed. At 80 % flow with 60 % static head the saving in the example is 45 kW of 194 kW.

Where do I get the throttled power?

From the fan or pump curve at the reduced flow and full speed (for inlet vanes, from the maker's vane curves). It is an input because it depends on the machine.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.