Peltier (Thermoelectric) Cooler Capacity and COP

Cooling capacity, electrical input and COP of a Peltier module at a current and temperatures, with the best current and the largest temperature difference.

Thermal power plant

Inputs

Examples: Illustrative 127 couples at 4 A, 40/10 CLow current 2 A, dT 10 KHigh current 8 A, dT 40 K

Accepted: 0.01 to 100 A
Accepted: -43.15 to 126.85 °C
Accepted: -123.15 to 126.85 °C
Accepted: 10 to 2,000 µV/K
Accepted: 1E-5 to 10 Ω
Accepted: 1E-8 to 0.001 kW/K
Accepted: 1 to 10,000

Results

Q_c = n(SIT_c − ½I²R − KΔT), P = n(SIΔT + I²R). Negative Q_c means the module cannot hold that temperature difference at this current. COP is typically 0.3–1, far below vapour-compression; Peltier coolers suit small loads, precise control and no moving parts.

Cooling capacity0.047000kW
Electrical input0.097536kW
Coefficient of performance0.48187
Module voltage12.192V
Current for maximum cooling S T_c/R11.126A
Largest temperature difference ½ZT_c²123.79K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 127 couples at 4 A, 40/10 C. The inputs, in the units selected above:

InputValue
Current4.0000 A
Hot-side temperature40.000 °C
Cold-side temperature10.000 °C
Seebeck coefficient per couple400.00 µV/K
Electrical resistance per couple0.010000 Ω
Thermal conductance per couple5.0000e-06 kW/K
Couples127.00 -

Applying the formula below gives:

ResultValue
Cooling capacity0.028326 kW
Electrical input0.026416 kW
Coefficient of performance1.0723
Module voltage6.6040 V
Current for maximum cooling S T_c/R11.326 A
Largest temperature difference ½ZT_c²128.28 K

Open this example in the calculator and change any input.

Formula

\(\dot Q_c = n\left(SIT_c - \frac{1}{2}I^2R - K\Delta T\right), \quad P_{in} = n\left(SI\Delta T + I^2R\right), \quad \Delta T_{max} = \frac{1}{2}ZT_c^2\)

Variables

Symbol Meaning SI unit
\(I\) Current A
\(T_h\) Hot-side temperature K
\(T_c\) Cold-side temperature K
\(S\) Seebeck coefficient per couple V/K
\(R\) Electrical resistance per couple Ω
\(K\) Thermal conductance per couple W/K
\(n\) Couples -
\(\dot Q_c\) Cooling capacity W
\(P_{in}\) Electrical input W
\(COP\) Coefficient of performance -
\(V\) Module voltage V
\(I_{max}\) Current for maximum cooling S T_c/R A
\(\Delta T_{max}\) Largest temperature difference ½ZT_c² K

Method and standards

Peltier cooling.

Where it is used

  • Electronics and laser cooling.
  • Small portable coolers.

Common mistakes

  • Ignoring the heat sink's temperature rise.
  • Running at maximum current for best efficiency.

Assumptions and limits

  • Constant properties; ideal heat sinks.

References

  • Thermoelectric cooling couple model

Questions and answers

Why is Peltier COP so low?

Joule heating and heat conduction back through the legs eat into the Peltier cooling; for ΔT of 30 K the COP is often below 1.

Is more current always better?

No: cooling peaks at I = ST_c/R and then falls as Joule heat grows, while power keeps rising, so the best COP is at a much lower current.

What do the defaults represent?

An illustrative 127-couple module (400 µV/K, 10 mΩ, 0.005 W/K per couple) at 4 A with 40 °C hot and 10 °C cold sides.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Kothari, Singal and Ranjan, Renewable Energy Sources and Emerging Technologies, 2nd ed. (PHI, 2011)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.