FireCADCalc

Explosion Overpressure by TNT Equivalence

TNT-equivalent mass of a vapour cloud or explosive, scaled distance and peak side-on overpressure at a distance from the Kinney–Graham curve fit.

Process steam and utilitiesDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 1 t hydrocarbon at 5 %, 100 m10 t propane at 3 %, 250 m1 kg TNT at 5 m

Results

TNT equivalence over-predicts near a vapour cloud explosion and under-predicts far away, because vapour clouds deflagrate; congested-area methods (TNO multi-energy, Baker–Strehlow) are better for plant layout.

A screening estimate for training and early design, not a hazard or risk study.

About 14–70 kPa: severe structural damage; lung haemorrhage becomes possible near the top of this range.

Equivalent mass of TNT1.0000kg
Scaled distance r/m_TNT^(1/3)5.0000
Peak side-on overpressure58.476kPa
Scaled overpressure0.57712

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1 t hydrocarbon at 5 %, 100 m. The inputs, in the units selected above:

InputValue
Mass of flammable material in the cloud1,000.0 kg
Heat of combustion (energy of explosion)46,000 kJ/kg
Explosion efficiency (1–10 % for vapour clouds)5.0000 %
Distance from the explosion centre100.00 m
Ambient pressure101.33 kPa

Applying the formula below gives:

ResultValue
Equivalent mass of TNT490.82 kg
Scaled distance r/m_TNT^(1/3)12.677
Peak side-on overpressure14.804 kPa
Scaled overpressure0.14611

Open this example in the calculator and change any input.

Formula

\(m_{TNT} = \frac{\eta\,m\,\Delta H_c}{E_{TNT}},\ E_{TNT} = 4686\ \text{kJ/kg}, \quad z_e = \frac{r}{m_{TNT}^{1/3}}\)

\(\frac{p^o}{p_a} = \frac{1616\left[1 + \left(\frac{z_e}{4.5}\right)^2\right]}{\sqrt{\left[1 + \left(\frac{z_e}{0.048}\right)^2\right]\left[1 + \left(\frac{z_e}{0.32}\right)^2\right]\left[1 + \left(\frac{z_e}{1.35}\right)^2\right]}}\)

Variables

Symbol Meaning SI unit
\(m\) Mass of flammable material in the cloud kg
\(\Delta H_c\) Heat of combustion (energy of explosion) J/kg
\(\eta\) Explosion efficiency (1–10 % for vapour clouds) -
\(r\) Distance from the explosion centre m
\(p_a\) Ambient pressure Pa
\(m_{TNT}\) Equivalent mass of TNT kg
\(z_e\) Scaled distance r/m_TNT^(1/3) -
\(p^o\) Peak side-on overpressure Pa
\(p^o/p_a\) Scaled overpressure -

Method and standards

TNT equivalence with the Kinney–Graham fit of the TNT overpressure curve (z_e in m/kg^(1/3)).

Where it is used

  • Siting of control rooms and occupied buildings (screening).
  • Training on explosion consequences.

Common mistakes

  • Using 100 % efficiency for vapour clouds.
  • Applying it close to a congested area without a congestion-based method.

Assumptions and limits

  • Hemispherical free-field blast; ideal TNT curve.

References

  • Crowl and Louvar
  • Chemical Process Safety: Fundamentals with Applications
  • 2nd ed. (Prentice Hall, 2002)
  • ch. 6
  • eqs. 6-25
  • 6-27 and 6-28 (Kinney and Graham)

Questions and answers

What explosion efficiency should I use?

Usually 1–10 % for vapour clouds, reflecting incomplete mixing and the low conversion of combustion energy into blast; 100 % for condensed explosives.

What overpressure breaks windows?

Around 1–2 kPa; light structures fail at about 7–14 kPa and reinforced buildings near 70 kPa.

What do the defaults represent?

1 t of hydrocarbon (46 MJ/kg) at 5 % efficiency, 100 m from the centre.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.