FireCADCalc

Static Electricity: Streaming Current, Voltage and Spark Energy

Streaming current in a pipe, charge and voltage built on an isolated vessel or drum, and the spark energy compared with a minimum ignition energy.

Process steam and utilitiesDistillery and ethanolRefinery and petrochemicalChemical and fertiliserTank and drum

Inputs

Examples: Toluene into a 100 pF drum, 60 sSlow fill 1 m/s, bonded person 200 pF

Results

The isolated container keeps all the charge (no leakage); bonding and grounding drains it. Low-conductivity liquids (relaxation time above about 0.1 s) are the hazard.

A screening estimate for training and early design, not a hazard or risk study.

Streaming current3.0482e-10A
Charge accumulated9.1445e-09C
Container voltage45.722V
Spark energy available2.0905e-04mJ
Spark energy over minimum ignition energy8.3622e-04

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Toluene into a 100 pF drum, 60 s. The inputs, in the units selected above:

InputValue
Liquid velocity in the pipe3.0000 m/s
Pipe diameter50.000 mm
Pipe length10.000 m
Liquid relaxation time21.000 s
Filling time60.000 s
Capacitance of the isolated container100.00 pF
Minimum ignition energy of the vapour0.10000 mJ

Applying the formula below gives:

ResultValue
Streaming current3.3024e-08 A
Charge accumulated1.9814e-06 C
Container voltage19,814 V
Spark energy available19.631 mJ
Spark energy over minimum ignition energy196.31

Open this example in the calculator and change any input.

Formula

\(I_s = 10\times10^{-6}(ud)^2\left[1 - \exp\left(-\frac{L}{u\tau}\right)\right], \quad Q = I_st, \quad V = \frac{Q}{C}, \quad J = \frac{Q^2}{2C}\)

Variables

Symbol Meaning SI unit
\(u\) Liquid velocity in the pipe m/s
\(d\) Pipe diameter m
\(L\) Pipe length m
\(\tau\) Liquid relaxation time s
\(t\) Filling time s
\(C\) Capacitance of the isolated container F
\(MIE\) Minimum ignition energy of the vapour J
\(I_s\) Streaming current A
\(Q\) Charge accumulated C
\(V\) Container voltage V
\(J\) Spark energy available J
\(J/MIE\) Spark energy over minimum ignition energy -

Method and standards

Streaming current (u in m/s, d in m, I in A) and capacitor energy.

Where it is used

  • Drum and tank filling with flammable solvents.
  • Training on bonding and grounding.

Common mistakes

  • Ignoring a person as a capacitor.
  • Assuming conductive liquids are hazardous.

Assumptions and limits

  • Isolated container; no charge leakage.

References

  • Crowl and Louvar
  • Chemical Process Safety: Fundamentals with Applications
  • 2nd ed. (Prentice Hall, 2002)
  • ch. 7
  • eqs. 7-21 to 7-27 (streaming current, charge, capacitance, energy)

Questions and answers

Why does a slow fill help?

Streaming current grows with the square of velocity: halving the velocity cuts the charge rate to a quarter.

What capacitance does a drum have?

Roughly 100 pF for an isolated 200 L drum, about 200–300 pF for a person, and much more for large tanks.

What do the defaults represent?

Toluene (relaxation time 21 s) at 3 m/s through 10 m of 50 mm pipe into an isolated 100 pF drum for 60 s.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.