Worked example
Example: Crowl and Louvar Example 3-8: toluene, 5 ft tank. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Molar mass of the liquid | 92.140 kg/kmol |
| Vapour pressure at the liquid temperature | 3.7597 kPa |
| Liquid temperature | 25.000 °C |
| Pool or liquid surface area | 1.8241 m² |
| Ventilation rate | 3,000.0 ft³/min |
| Non-ideal mixing factor (0.1–0.5) | 0.10000 - |
| Ambient pressure | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Gas-phase mass transfer coefficient | 0.004816 m/s |
| Evaporation rate | 4.4196 kg/h |
| Vapour concentration in the room (ppm by volume) | 2,302.3 |
Open this example in the calculator and change any input.
Formula
\(K = K_0\left(\frac{M_0}{M}\right)^{1/3},\ K_0 = 0.83\ \text{cm/s},\ M_0 = 18, \quad Q_m = \frac{MKAP^{sat}}{R_gT_L}, \quad C_{ppm} = \frac{Q_mR_gT}{kQ_vPM}\times10^6\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(M\) | Molar mass of the liquid | kg/kmol |
| \(P^{sat}\) | Vapour pressure at the liquid temperature | Pa |
| \(T_L\) | Liquid temperature | K |
| \(A\) | Pool or liquid surface area | m² |
| \(Q_v\) | Ventilation rate | m³/s |
| \(k\) | Non-ideal mixing factor (0.1–0.5) | - |
| \(P\) | Ambient pressure | Pa |
| \(K\) | Gas-phase mass transfer coefficient | m/s |
| \(Q_m\) | Evaporation rate | kg/s |
| \(C_{ppm}\) | Vapour concentration in the room (ppm by volume) | - |
Method and standards
Mass transfer from the liquid surface into still air, with dilution ventilation.
Where it is used
- Open tanks, drums and spills indoors.
- Ventilation design for solvent handling.
Common mistakes
- Using it for boiling liquids.
- Ignoring wind outdoors.
Assumptions and limits
- Low vapour pressure; still air.
References
- Crowl and Louvar
- Chemical Process Safety: Fundamentals with Applications
- 2nd ed. (Prentice Hall, 2002)
- ch. 3
- eqs. 3-12 to 3-18
- Example 3-8
Questions and answers
Why use water as the reference?
Its mass transfer coefficient over a pool in still air is well known (0.83 cm/s); other liquids scale with (18/M)^(1/3).
What is k?
A factor for imperfect mixing in the room: the real concentration near the source is higher than the well-mixed value, so k < 1.
What do the defaults represent?
Crowl and Louvar's Example 3-8: toluene at 25 °C from a 5 ft (1.52 m) tank, 3,000 ft³/min ventilation, k = 0.1.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.