FireCADCalc

Product Cooling and Freezing Load

Heat to remove when a product is cooled, frozen and sub-cooled (sensible, latent of its water, sensible below freezing) and the load over the pull-down time.

Food, dairy and textile

Inputs

Examples: 10 t meat 20 → −18 °C in 24 hChilling only 20 → 4 °C

Results

The load is the average over the pull-down; the peak at the start is higher.

Add packaging, respiration (fresh produce), infiltration and fan heat for the room load.

Sensible heat above freezing792.00MJ
Latent heat2,334.8MJ
Sensible heat below freezing288.00MJ
Total3,414.8MJ
Average refrigeration load39.524kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 t meat 20 → −18 °C in 24 h. The inputs, in the units selected above:

InputValue
Product10,000 kg
Specific heat above freezing3.6000 kJ/(kg·K)
Specific heat below freezing1.8000 kJ/(kg·K)
Water that freezes (share of mass)70.000 %
Initial temperature20.000 °C
Initial freezing point-2.0000 °C
Final temperature-18.000 °C
Pull-down time24.000 h

Applying the formula below gives:

ResultValue
Sensible heat above freezing792.00 MJ
Latent heat2,334.8 MJ
Sensible heat below freezing288.00 MJ
Total3,414.8 MJ
Average refrigeration load39.524 kW

Open this example in the calculator and change any input.

Formula

\(Q_1 = Mc_u\max\left[T_1 - \max(T_f, T_2), 0\right], \quad Q_2 = Mw_f\lambda_f\ (T_2 < T_f), \quad Q_3 = Mc_f\max\left[\min(T_f, T_1) - T_2, 0\right]\)

\(Q = Q_1 + Q_2 + Q_3, \quad \dot Q = \frac{Q}{t}\)

Variables

Symbol Meaning SI unit
\(M\) Product kg
\(c_u\) Specific heat above freezing J/(kg·K)
\(c_f\) Specific heat below freezing J/(kg·K)
\(w_f\) Water that freezes (share of mass) -
\(T_1\) Initial temperature K
\(T_f\) Initial freezing point K
\(T_2\) Final temperature K
\(t\) Pull-down time s
\(Q_1\) Sensible heat above freezing J
\(Q_2\) Latent heat J
\(Q_3\) Sensible heat below freezing J
\(Q\) Total J
\(\dot Q\) Average refrigeration load W
\(\lambda_f\) Latent heat of fusion of ice, 333 550 J/kg

Method and standards

Sensible and latent heat balance.

Where it is used

  • Blast freezer and cold store sizing.

Common mistakes

  • Ignoring the latent heat.
  • Using total water as frozen water.

Assumptions and limits

  • Freezing at one temperature.
  • A product entered at or below its freezing point is taken as unfrozen (supercooled) and the full latent heat is counted; for product already frozen, Q is high by M w_f λ_f.
  • The load is an average over the pull-down time; the peak at the start is higher.

References

  • Mass and energy balances (definitions); latent heat of fusion of ice 333.55 kJ/kg

Questions and answers

Why is latent heat so large?

Freezing water takes 334 kJ/kg, as much as cooling water by 80 K.

Is all the water frozen?

No; some stays unfrozen at storage temperature, so w_f is less than the total water.

Why a lower specific heat below freezing?

Ice has about half the specific heat of water.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators