Fuel Oil Tank Heating Coil Area and Steam

Steam coil area and steam flow to heat a fuel oil storage or day tank in a given time, including the tank's heat loss, from oil mass, temperatures and U values.

Thermal power plantSugar mill and cogenerationPulp and paperIAPWS-IF97 (water and steam)Fuel oil and gas systemTank and drum

Inputs

Examples: 200 t tank, 30 to 60 °C in 24 h, 7 bar(a) steam50 t day tank, 40 to 70 °C in 12 h, 4 bar(a)1000 t storage, 25 to 45 °C in 48 h, 10 bar(a)

About 1 W/(m²·K) insulated, 5–7 bare; wind raises it.
Low for viscous oil in natural convection; from the heater maker or plant data.
Shown as gauge (bar g, kg/cm² g, psig) as plant headers read; choose an absolute unit to enter absolute pressure.

Results

Coil area needed14.470m²
Steam consumption412.14kg/h
Total heat duty230.62kW
Heat to raise the oil temperature214.12kW
Tank heat loss at mean temperature16.500kW
Steam saturation temperature179.89°C

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 200 t tank, 30 to 60 °C in 24 h, 7 bar(a) steam. The inputs, in the units selected above:

InputValue
Oil in the tank200.00 t
Mean specific heat of the oil1.9000 kJ/(kg·K)
Oil temperature at start30.000 °C
Oil temperature wanted60.000 °C
Heating time24.000 h
Tank surface area losing heat300.00 m²
Tank heat-loss coefficient1.2000 W/(m²·K)
Ambient temperature25.000 °C
Coil overall heat transfer coefficient120.00 W/(m²·K)
Heating steam pressure (saturated)5.9867 bar g

Applying the formula below gives:

ResultValue
Coil area needed9.6666 m²
Steam consumption242.51 kg/h
Total heat duty139.14 kW
Heat to raise the oil temperature131.94 kW
Tank heat loss at mean temperature7.2000 kW
Steam saturation temperature164.95 °C

Open this example in the calculator and change any input.

Formula

\(\dot Q_h = \frac{M\,c_p\,(T_2 - T_1)}{t} \qquad \dot Q_l = U_t\,A_t\,(T_m - T_a),\ T_m = \frac{T_1 + T_2}{2} \qquad \dot Q = \dot Q_h + \dot Q_l\)

\(A_c = \frac{\dot Q}{U_c\,(T_{sat} - T_m)} \qquad \dot m_s = \frac{\dot Q}{h_{fg}(p_s)}\)

Variables

Symbol Meaning SI unit
\(M\) oil in the tank kg
\(c_p\) mean specific heat of the oil J/(kg·K)
\(T_1\) oil temperature at start K
\(T_2\) oil temperature wanted K
\(t\) heating time s
\(A_t\) tank surface losing heat m²
\(U_t\) tank heat-loss coefficient W/(m²·K)
\(T_a\) ambient temperature K
\(U_c\) coil overall coefficient W/(m²·K)
\(p_s\) steam pressure (absolute in SI; shown as gauge) Pa
\(A_c\) coil area m²
\(\dot m_s\) steam consumption kg/s
\(\dot Q\) total duty W
\(\dot Q_h\) heat to raise the oil W
\(\dot Q_l\) tank heat loss W
\(T_{sat}\) steam saturation temperature K
\(T_m\) mean oil temperature K
\(h_{fg}\) latent heat (IF97) J/kg

Method and standards

Energy balance of the tank over the heating time, with the heat loss at the mean oil temperature; coil area by the steam-to-mean-oil temperature difference; steam latent heat from FireCAD's IAPWS-IF97.

Where it is used

  • Designing heating coils for storage and day tanks.
  • Steam budgets for oil terminals and boiler houses.
  • Checking heating time after a coil is damaged or fouled.

Common mistakes

  • Ignoring the tank loss on windy, uninsulated tanks.
  • Using a forced-convection U for a still tank.
  • Forgetting condensate drainage: a flooded coil loses most of its area.

Assumptions and limits

  • Well-mixed oil; constant properties; condensate leaves saturated.
  • The coil area uses the difference between the steam and the mean oil temperature. The exact batch-heating result, \(A = M c_p \ln[(T_{sat} - T_1)/(T_{sat} - T_2)]/(U_c t)\), is close when the steam is much hotter than the oil but larger as \(T_{sat}\) approaches \(T_2\); a note appears within 15 K.
  • Below ambient the tank gains heat and the loss is negative, with a note.

References

  • IAPWS R7-97(2012) IF97
  • first law of thermodynamics

Questions and answers

How big a coil does an oil tank need?

Heat duty over U times the temperature difference. Heating 200 t of oil from 30 to 60 °C in 24 hours takes 132 kW plus 7 kW of tank loss; with 7 bar(a) steam and U = 120 W/(m²·K) the coil needs 9.7 m² and about 242 kg/h of steam.

Why is the coil U so low?

Viscous oil moves by natural convection only, so the oil side controls; 50–200 W/(m²·K) is common. A suction heater with forced flow does far better.

Should I keep the whole tank hot?

Often not: a suction heater warms only the oil being drawn, while the tank is kept just above pumping temperature.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.