Time to Heat a Particle or Fuel Feed in a Fluidised Bed

Time for a particle (fuel, sorbent or make-up) to approach bed temperature from the gas-to-particle coefficient, with the 99 % time (Basu Eqs. 3.3–3.4).

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperBoiler

Inputs

Examples: 300 µm sand into an 850 °C bed3 mm limestone6 mm coal (Biot above 0.1)

About 1 to 3 W/(m·K) for sand and limestone, 0.2 to 0.3 for coal, 0.1 to 0.2 for biomass. Used only for the Biot number check.

Results

Biot number 0.8 is above 0.1: the particle centre lags its surface and the lumped time shown is too short. Use a transient conduction solution (Heisler charts) for this size.

Time to reach T_p5.4605s
Time to close 99 % of the gap41.769s
Biot number h d_p/(6 k_p)0.80000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 300 µm sand into an 850 °C bed. The inputs, in the units selected above:

InputValue
Particle specific heat0.84000 kJ/(kg·K)
Particle density2,500.0 kg/m³
Mean particle diameter (surface-volume)0.30000 mm
Gas-to-particle heat transfer coefficient200.00 W/(m²·K)
Bed (gas) temperature850.00 °C
Initial particle temperature30.000 °C
Particle temperature to reach800.00 °C
Particle thermal conductivity1.5000 W/(m·K)

Applying the formula below gives:

ResultValue
Time to reach T_p1.4686 s
Time to close 99 % of the gap2.4097 s
Biot number h d_p/(6 k_p)0.006667

Open this example in the calculator and change any input.

Formula

\(t = \frac{C_p\rho_pd_p}{6h_{gp}}\ln\frac{T_g - T_{p0}}{T_g - T_p}, \quad t_{99\%} = 0.765\frac{C_p\rho_pd_p}{h_{gp}}\)

Variables

Symbol Meaning SI unit
\(C_p\) Particle specific heat J/(kg·K)
\(\rho_p\) Particle density kg/m³
\(d_p\) Mean particle diameter (surface-volume) m
\(h_{gp}\) Gas-to-particle heat transfer coefficient W/(m²·K)
\(T_g\) Bed (gas) temperature K
\(T_{p0}\) Initial particle temperature K
\(T_p\) Particle temperature to reach K
\(t\) Time to reach T_p s
\(t_{99\%}\) Time to close 99 % of the gap s
\(k_p\) Particle thermal conductivity W/(m·K)
\(Bi\) Biot number h d_p/(6 k_p) -

Method and standards

Lumped-capacity heating of a sphere.

Where it is used

  • Fuel feeding and combustion studies.

Common mistakes

  • Using the lumped model for large lumps.

Assumptions and limits

  • Uniform particle temperature; constant h.
  • Valid only for a Biot number Bi = h d_p / (6 k_p) below about 0.1, which the calculator shows and warns about. For coarse coal of several millimetres internal conduction slows heating and the time shown is too short.

References

  • Basu
  • Circulating Fluidized Bed Boilers: Design
  • Operation and Maintenance (Springer, 2015)
  • ch. 3
  • Eqs. (3.3) and (3.4) (lumped particle heating)

Questions and answers

Why so fast?

Small particles have little mass per surface: a 300 µm sand grain closes 99 % of the gap in about 2–3 s at h = 200 W/m²·K.

Why 0.765?

It is Basu's coefficient for the time to close 99 % of the gap for a sphere with lumped capacity; ln(100)/6 = 0.768, so the two agree within 0.3 %.

Is the lumped model valid?

For small particles (Biot number < 0.1); large coal lumps heat more slowly inside.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.