Cooling Tower KaV/L (Merkel Number)

Tower characteristic KaV/L by the Merkel equation with the four-point Chebyshev integration, from hot and cold water temperatures, wet bulb and L/G ratio.

Thermal power plantSugar mill and cogenerationRefinery and petrochemicalChemical and fertiliserIAPWS-IF97 (water and steam)Condenser and cooling tower

Inputs

Examples: 41 to 32 °C, wet bulb 27 °C, L/G 1.138 to 31 °C, wet bulb 26 °C, L/G 1.2540 to 29 °C, wet bulb 22 °C, L/G 0.9

Results

Tower characteristic (Merkel number)1.1232
Range9.0000K
Approach5.0000K
Exit air enthalpy per kg dry air126.44kJ/kg

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 41 to 32 °C, wet bulb 27 °C, L/G 1.1. The inputs, in the units selected above:

InputValue
Hot water temperature41.000 °C
Cold water temperature32.000 °C
Inlet air wet-bulb temperature27.000 °C
Liquid-to-gas ratio (water per kg of dry air)1.1000 kg/kg
Atmospheric pressure1.0132 bar

Applying the formula below gives:

ResultValue
Tower characteristic (Merkel number)1.1232
Range9.0000 K
Approach5.0000 K
Exit air enthalpy per kg dry air126.44 kJ/kg

Open this example in the calculator and change any input.

Formula

\(\frac{KaV}{L} = \int_{T_{cold}}^{T_{hot}} \frac{c_w\,dT}{h_w - h_a} \approx \frac{c_w\,R}{4}\sum_{i=1}^{4}\frac{1}{h_{w,i} - h_{a,i}}\)

\(T_i = T_{cold} + \{0.1, 0.4, 0.6, 0.9\}\,R \qquad h_{a,i} = h_{a,1} + \frac{L}{G}\,c_w\,(T_i - T_{cold}) \qquad h_{a,2} = h_{a,1} + \frac{L}{G}\,c_w\,R\)

\(h_{sat}(t) = c_{p,da}\,t + W_s\,(h_{g0} + c_{p,v}\,t) \qquad W_s = \frac{M_w}{M_{da}}\,\frac{p_s}{p - p_s}\)

Variables

Symbol Meaning SI unit
\(T_{hot}\) hot water temperature K
\(T_{cold}\) cold water temperature K
\(T_{wb}\) inlet air wet-bulb temperature K
\(L/G\) liquid-to-gas ratio kg/kg
\(p\) atmospheric pressure Pa
\(KaV/L\) tower characteristic (Merkel number) –
\(R\) range K
\(A\) approach, \(T_{cold} - T_{wb}\) K
\(h_{a,2}\) exit air enthalpy J/kg
\(h_{a,1}\) inlet air enthalpy, saturated at \(T_{wb}\) J/kg
\(h_w\), \(h_{sat}\) saturated air enthalpy at water temperature J/kg
\(h_a\) air enthalpy along the tower J/kg
\(c_w\) specific heat of water (IF97, mean temperature) J/(kg·K)
\(t\) temperature in °C °C
\(W_s\) saturation humidity ratio kg/kg
\(p_s\) saturation pressure of water (IF97) Pa
\(c_{p,da}\), \(c_{p,v}\), \(h_{g0}\) 1006 J/(kg·K), 1860 J/(kg·K), 2 501 000 J/kg (ASHRAE) –
\(M_w\), \(M_{da}\) molar masses of water and dry air kg/kmol

Method and standards

Merkel's equation with the usual simplifications (Lewis factor 1, evaporation loss neglected), integrated by the four-point Chebyshev rule used in cooling tower practice. Inlet air enthalpy is taken as saturated air at the wet bulb. Moist-air enthalpy by the ASHRAE ideal-gas expression; saturation pressure and water specific heat by FireCAD's IAPWS-IF97.

Where it is used

  • Checking whether a tower can meet a new duty or a hotter design wet bulb.
  • Comparing fills and towers on the same demand basis.
  • Thermal acceptance testing support, alongside the maker's curves.

Common mistakes

  • Using dry-bulb temperature for the inlet air.
  • Comparing KaV/L values computed with different integration methods or water specific heats.
  • Forgetting that the result depends strongly on the approach: small approaches give very large KaV/L.

Assumptions and limits

  • Counterflow; Lewis factor 1; no evaporation loss in the water balance; air leaves unsaturated or just saturated.
  • The driving force is checked only at the four Chebyshev points; the air line could touch the saturation curve between them, and the four-point rule is less accurate at a small approach (below about 3 K).
  • \(G\) in L/G is the dry-air mass flow, matching the enthalpy per kg of dry air.
  • Wet bulb from 0.01 °C (the triple point) upwards: the saturation pressure is that over liquid water, so sub-zero wet bulbs are not accepted.

References

  • F. Merkel (1925) evaporative cooling theory
  • four-point Chebyshev integration as used in cooling tower practice
  • ASHRAE Handbook—Fundamentals (2017) ch. 1 moist-air enthalpy
  • IAPWS R7-97(2012) IF97

Questions and answers

What is KaV/L?

The tower's required "number of transfer units": how much contact between water and air the duty demands. Cooling from 41 to 32 °C with a 27 °C wet bulb at L/G 1.1 needs KaV/L = 1.12.

How is it calculated?

The Merkel integral of c_w dT / (h_w − h_a) over the range, evaluated by the Chebyshev rule at 10, 40, 60 and 90 % of the range. h_w is saturated air enthalpy at the water temperature and h_a the air enthalpy, which rises by L/G · c_w per kelvin.

What do I do with the number?

Compare it with the fill's characteristic from the maker (KaV/L = C (L/G)^−n). Where they meet is the tower's operating point; a demand above the fill's capability means the tower cannot reach that cold water temperature.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.