Cooling Tower L/G Ratio, Heat Rejection and Fan Power

Liquid-to-gas ratio, heat rejected, air volume and fan shaft and motor power of a mechanical-draught cooling tower from water and air flows.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 3,000 t/h, 10 K, 2,700 t/h airSmall tower 500 t/h, 6 K

Results

Typical L/G for counterflow towers is 0.8–1.5; fan power is usually 0.5–1 % of the heat rejected. The tower's capability against L/G comes from the Merkel calculator or the supplier's curve.

Liquid-to-gas ratio1.2500kg/kg
Heat rejected3.4883MW
Air volume at the fan357,143m³/h
Fan shaft power18.315kW
Motor input power20.813kW
Fan motor power as a share of heat rejected (1 % = 10 kW per MW)0.59663%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 3,000 t/h, 10 K, 2,700 t/h air. The inputs, in the units selected above:

InputValue
Circulating water flow3,000.0 t/h
Range (hot − cold water)10.000 K
Dry air flow2,700.0 t/h
Density of the moist air at the fan1.1000 kg/m³
Fan static pressure150.00 Pa
Fan static efficiency70.000 %
Motor and drive efficiency90.000 %

Applying the formula below gives:

ResultValue
Liquid-to-gas ratio1.1111 kg/kg
Heat rejected34.883 MW
Air volume at the fan2,454,545 m³/h
Fan shaft power146.10 kW
Motor input power162.34 kW
Fan motor power as a share of heat rejected (1 % = 10 kW per MW)0.46537 %

Open this example in the calculator and change any input.

Formula

\(L/G = \frac{\dot m_w}{\dot m_a}, \quad Q = \dot m_wc_pR, \quad P_f = \frac{\dot m_a}{\rho_a}\frac{\Delta p_s}{\eta_f}\)

Variables

Symbol Meaning SI unit
\(\dot m_w\) Circulating water flow kg/s
\(R\) Range (hot − cold water) K
\(\dot m_a\) Dry air flow kg/s
\(\rho_a\) Air density at the fan kg/m³
\(\Delta p_s\) Fan static pressure Pa
\(\eta_f\) Fan static efficiency -
\(\eta_m\) Motor and drive efficiency -
\(L/G\) Liquid-to-gas ratio kg/kg
\(Q\) Heat rejected W
\(\dot V_a\) Air volume at the fan m³/s
\(P_f\) Fan shaft power W
\(P_m\) Motor input power W
\(P_m/Q\) Fan motor power as a share of heat rejected -
\(c_p\) specific heat of water, 4186 J/(kg·K)

Method and standards

Heat and mass balance definitions.

Where it is used

  • Cooling tower checks and fan replacement.
  • Energy audits.

Common mistakes

  • Using wet-bulb air density at the fan outlet for an induced-draught fan.
  • Mixing total and static efficiency.

Assumptions and limits

  • Static pressure and efficiency on the same basis.
  • Water \(c_p\) constant at 4.186 kJ/(kg·K).
  • The air volume is the dry-air mass over the moist-air density at the fan. For an induced-draught fan the air is warm and saturated, and its water vapour adds a few per cent to the volume, so the fan volume and power are slightly understated.

References

  • Cooling tower definitions; fan power P = V̇Δp/η

Questions and answers

Why does L/G matter?

It sets how much air each kilogram of water meets; lower L/G (more air) gives a closer approach but more fan power.

What fan pressure is typical?

100–250 Pa static for induced-draught cells.

What do the defaults give?

3,000 t/h at 10 K range with 2,700 t/h of air: L/G 1.11, 34.9 MW rejected, about 160 kW of motor power (0.47 %).

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.