Worked example
Example: 3,000 t/h, 10 K, 2,700 t/h air. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Circulating water flow | 3,000.0 t/h |
| Range (hot − cold water) | 10.000 K |
| Dry air flow | 2,700.0 t/h |
| Density of the moist air at the fan | 1.1000 kg/m³ |
| Fan static pressure | 150.00 Pa |
| Fan static efficiency | 70.000 % |
| Motor and drive efficiency | 90.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Liquid-to-gas ratio | 1.1111 kg/kg |
| Heat rejected | 34.883 MW |
| Air volume at the fan | 2,454,545 m³/h |
| Fan shaft power | 146.10 kW |
| Motor input power | 162.34 kW |
| Fan motor power as a share of heat rejected (1 % = 10 kW per MW) | 0.46537 % |
Open this example in the calculator and change any input.
Formula
\(L/G = \frac{\dot m_w}{\dot m_a}, \quad Q = \dot m_wc_pR, \quad P_f = \frac{\dot m_a}{\rho_a}\frac{\Delta p_s}{\eta_f}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_w\) | Circulating water flow | kg/s |
| \(R\) | Range (hot − cold water) | K |
| \(\dot m_a\) | Dry air flow | kg/s |
| \(\rho_a\) | Air density at the fan | kg/m³ |
| \(\Delta p_s\) | Fan static pressure | Pa |
| \(\eta_f\) | Fan static efficiency | - |
| \(\eta_m\) | Motor and drive efficiency | - |
| \(L/G\) | Liquid-to-gas ratio | kg/kg |
| \(Q\) | Heat rejected | W |
| \(\dot V_a\) | Air volume at the fan | m³/s |
| \(P_f\) | Fan shaft power | W |
| \(P_m\) | Motor input power | W |
| \(P_m/Q\) | Fan motor power as a share of heat rejected | - |
| \(c_p\) | specific heat of water, 4186 | J/(kg·K) |
Method and standards
Heat and mass balance definitions.
Where it is used
- Cooling tower checks and fan replacement.
- Energy audits.
Common mistakes
- Using wet-bulb air density at the fan outlet for an induced-draught fan.
- Mixing total and static efficiency.
Assumptions and limits
- Static pressure and efficiency on the same basis.
- Water \(c_p\) constant at 4.186 kJ/(kg·K).
- The air volume is the dry-air mass over the moist-air density at the fan. For an induced-draught fan the air is warm and saturated, and its water vapour adds a few per cent to the volume, so the fan volume and power are slightly understated.
References
- Cooling tower definitions; fan power P = V̇Δp/η
Questions and answers
Why does L/G matter?
It sets how much air each kilogram of water meets; lower L/G (more air) gives a closer approach but more fan power.
What fan pressure is typical?
100–250 Pa static for induced-draught cells.
What do the defaults give?
3,000 t/h at 10 K range with 2,700 t/h of air: L/G 1.11, 34.9 MW rejected, about 160 kW of motor power (0.47 %).
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.