Condenser Tube Count and Water Velocity

Number of tubes per pass and in total for a condenser or shell-and-tube cooler from cooling water flow, tube size, passes and design velocity, with the actual velocity.

Thermal power plantSugar mill and cogenerationChemical and fertiliserPulp and paperCondenser and cooling tower

Inputs

Examples: 2400 m³/h, 19.05 mm x 0.71 mm tubes, 2 passes, 2 m/s, 8 m900 m³/h, 25.4 x 1.24 mm, 2 passes, 1.8 m/s, 6 m30000 m³/h, 25.4 x 0.71 mm, 1 pass, 2.2 m/s, 12 m

A common design range is 1.5–2.5 m/s: lower fouls, higher erodes; the tube material sets the upper limit (take it from the tube maker).

Results

Tubes per pass8,388.0
Total tubes8,388.0
Actual water velocity2.1997m/s
Tube inside diameter23.980mm
Outside tube surface8,032.0m²

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2400 m³/h, 19.05 mm x 0.71 mm tubes, 2 passes, 2 m/s, 8 m. The inputs, in the units selected above:

InputValue
Cooling water flow2,400.0 m³/h
Tube outside diameter19.050 mm
Tube wall thickness0.71000 mm
Number of water passes2.0000 -
Design water velocity in the tubes2.0000 m/s
Effective tube length8.0000 m

Applying the formula below gives:

ResultValue
Tubes per pass1,366.0
Total tubes2,732.0
Actual water velocity1.9992 m/s
Tube inside diameter17.630 mm
Outside tube surface1,308.0 m²

Open this example in the calculator and change any input.

Formula

\(d_i = d_o - 2\,t_w \qquad n_p = \left\lceil \frac{\dot V}{v \cdot \pi d_i^2/4} \right\rceil \qquad n = n_p\,N_p\)

\(v_{act} = \frac{\dot V}{n_p\,\pi d_i^2/4} \qquad A_o = n\,\pi\,d_o\,L\)

Variables

Symbol Meaning SI unit
\(\dot V\) cooling water flow m³/s
\(d_o\) tube outside diameter m
\(t_w\) tube wall thickness m
\(N_p\) number of water passes –
\(v\) design water velocity m/s
\(L\) effective tube length m
\(n_p\) tubes per pass –
\(n\) total tubes –
\(v_{act}\) actual water velocity m/s
\(d_i\) tube inside diameter m
\(A_o\) outside tube surface m²

Method and standards

Continuity: every pass carries the whole flow, so tubes per pass follow from flow, velocity and the tube bore, rounded up to a whole tube.

Where it is used

  • Laying out surface condensers, oil coolers and other shell-and-tube coolers.
  • Checking tube velocity after a change of cooling water flow.
  • Estimating the tube sheet size and number of tubes to buy.

Common mistakes

  • Using the outside diameter for the flow area.
  • Forgetting plugged tubes, which raise the velocity in the others.
  • Counting each pass's tubes as carrying part of the flow.

Assumptions and limits

  • Equal flow in all tubes; straight tubes; plugging margin not included: add spare tubes for the plugging you expect.
  • The actual velocity is not checked against a limit; the 1.5–2.5 m/s range in the help is common design practice, and the tube maker sets the limit for the material.

References

  • Continuity equation (flow = velocity × area)

Questions and answers

How many tubes does a condenser need?

Enough per pass to carry the water at the design velocity. 2400 m³/h at 2 m/s in 19.05 × 0.71 mm tubes needs 1366 tubes per pass; with two passes that is 2732 tubes and, 8 m long, 1308 m² of outside surface.

What water velocity is right?

Usually 1.5–2.5 m/s. Lower velocities let silt and scale settle; higher ones erode the tube inlets and raise pumping power. The tube material sets the limit.

Does the area match the required area?

Compare the outside surface here with the area from the condenser surface area calculator; adjust length or tube count until both agree.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.