Surface Condenser Test: TTD, Subcooling, Duty and UA

Terminal and initial temperature differences, condensate subcooling, duty, LMTD and UA of a surface condenser from a test of pressure and water temperatures.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliserIAPWS-IF97 (water and steam)

Inputs

Examples: 8.5 kPa(a), 28 → 38 °C, 10,000 t/h, 3,000 m²Fouled: 10 kPa(a), 30 → 39 °C, hotwell 5 K subcooled

Results

Saturation temperature42.665°C
Terminal temperature difference4.6645K
Initial temperature difference14.665K
Condensate subcooling1.1645K
Duty116.28MW
LMTD8.7302K
Overall coefficient4,439.7W/(m²·K)

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 8.5 kPa(a), 28 → 38 °C, 10,000 t/h, 3,000 m². The inputs, in the units selected above:

InputValue
Condenser pressure (absolute)8.5000 kPa
Cooling water inlet28.000 °C
Cooling water outlet38.000 °C
Condensate (hotwell) temperature41.500 °C
Cooling water flow10,000 t/h
Condenser surface area3,000.0 m²

Applying the formula below gives:

ResultValue
Saturation temperature42.665 °C
Terminal temperature difference4.6645 K
Initial temperature difference14.665 K
Condensate subcooling1.1645 K
Duty116.28 MW
LMTD8.7302 K
Overall coefficient4,439.7 W/(m²·K)

Open this example in the calculator and change any input.

Formula

\(TTD = T_s - t_2, \quad ITD = T_s - t_1, \quad Q = \dot m_wc_p(t_2 - t_1), \quad \Delta T_{lm} = \frac{t_2 - t_1}{\ln\frac{T_s - t_1}{T_s - t_2}}, \quad U = \frac{Q}{A\,\Delta T_{lm}}\)

Variables

Symbol Meaning SI unit
\(p_c\) Condenser pressure (absolute) Pa
\(t_1\) Cooling water inlet K
\(t_2\) Cooling water outlet K
\(T_c\) Condensate (hotwell) temperature K
\(\dot m_w\) Cooling water flow kg/s
\(A\) Condenser surface area m²
\(T_s\) Saturation temperature K
\(TTD\) Terminal temperature difference K
\(ITD\) Initial temperature difference K
\(\Delta T_{sub}\) Condensate subcooling K
\(Q\) Duty W
\(\Delta T_{lm}\) LMTD K
\(U\) Overall coefficient, on the outside tube area W/(m²·K)
\(c_p\) specific heat of water, 4186 J/(kg·K)

Method and standards

Heat and mass balance definitions; condensing side at saturation.

Where it is used

  • Condenser performance monitoring.
  • Deciding on tube cleaning.

Common mistakes

  • Using gauge vacuum instead of absolute pressure.
  • Reading CW outlet temperature downstream of a bypass.

Assumptions and limits

  • Steady load; c_p of water 4.186 kJ/(kg·K) (about 0.2 % above the IF97 value at 30–40 °C).
  • The area must be the outside tube surface the condenser maker quotes.

References

  • Babcock & Wilcox
  • Steam: Its Generation and Use
  • 41st ed. (2005)
  • ch. 21 (condenser performance)
  • Saturation from IAPWS-IF97

Questions and answers

What is TTD?

Saturation temperature at the condenser pressure minus the cooling water outlet temperature; 2.5–5 K is typical. A rising TTD at the same load means fouling or air.

Why watch subcooling?

Condensate colder than saturation wastes heat and carries more dissolved oxygen; it usually means air blanketing.

What do the defaults give?

8.5 kPa(a) (42.7 °C), water 28 → 38 °C at 10,000 t/h: TTD 4.7 K, 116 MW, U about 4,400 W/(m²·K).

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.