Worked example
Example: 100 KLPD. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Plant capacity (absolute alcohol) | 100.00 kL/d |
| Dilution (process) water per kL | 6.0000 - |
| Cooling-tower make-up per kL | 5.0000 - |
| Boiler and utility make-up per kL | 1.5000 - |
| Condensate recycled per kL | 6.5000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total water use per kL | 12.500 |
| Fresh water per kL | 6.0000 |
| Fresh water per day | 600.00 m³/d |
| Recycle share | 52.000 % |
Open this example in the calculator and change any input.
Formula
\(w_t = w_d + w_c + w_b, \quad w_f = \max(0, w_t - w_r), \quad \dot V_f = \dot V_e w_f\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V_e\) | Plant capacity (absolute alcohol) | m³/s |
| \(w_d\) | Dilution (process) water per kL | - |
| \(w_c\) | Cooling-tower make-up per kL | - |
| \(w_b\) | Boiler and utility make-up per kL | - |
| \(w_r\) | Condensate recycled per kL | - |
| \(w_t\) | Total water use per kL | - |
| \(w_f\) | Fresh water per kL | - |
| \(\dot V_f\) | Fresh water per day | m³/s |
| \(w_r/w_t\) | Recycle share | - |
Method and standards
Water balance.
Where it is used
- Consent compliance.
- Water audits.
Common mistakes
- Gross condensate counted before polishing reject.
Assumptions and limits
- Steady operation.
References
- Water balance per kL of alcohol (m³ per kL)
Questions and answers
What do consents ask for?
Specific fresh water use per kL of alcohol, with a ZLD condition for many plants.
Biggest saving?
Recycling polished evaporator and process condensate into dilution and cooling make-up.
Units?
m³ of water per kL of alcohol, which is the same as L per L.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.