Pump Motor Rating (kW with Margin)

Motor rating for a pump: power absorbed from flow, head and efficiency, plus the motor margin, rounded up to the next IEC standard motor rating.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserHydraulic Institute (pumps)PumpElectric motor

Inputs

Examples: Transfer pump 30 m³/h, 45 m, 68 %, +18 %Boiler feed pump 65 m³/h, 900 m, 955 kg/m³, 70 %, +18 %Shaft power 41 kW entered, +18 %

18 % for pump motors. Default from FireCAD design practice; enter your specification's value.

Flow, head and efficiency

From the pump maker's curve at the duty point. 68 % is a typical maker's value for this size; some makers offer better. Default from FireCAD design practice; enter your specification's value.

Shaft power entered

Results

Standard motor rating (IEC 60072-1)55.000kW
Minimum motor rating (absorbed + margin)48.380kW
Power absorbed at the pump shaft41.000kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Transfer pump 30 m³/h, 45 m, 68 %, +18 %. The inputs, in the units selected above:

InputValue
Power absorbed fromFlow, head and efficiency
Flow30.000 m³/h
Total head45.000 m
Liquid density998.00 kg/m³
Pump efficiency68.000 %
Pump shaft power (from the maker's data)0 kW
Motor margin over the power absorbed18.000 %

Applying the formula below gives:

ResultValue
Standard motor rating (IEC 60072-1)7.5000 kW
Minimum motor rating (absorbed + margin)6.3688 kW
Power absorbed at the pump shaft5.3973 kW
Hydraulic power3.6701 kW

Open this example in the calculator and change any input.

Formula

\(P_h = \rho\,g\,Q\,H \qquad P_s = \frac{P_h}{\eta_p}\ \ \text{(or } P_{s,in}\text{ entered)} \qquad P_{m,min} = P_s\,(1 + m_m)\)

\(P_{std}\) is the smallest standard rating at or above \(P_{m,min}\).

Variables

Symbol Meaning SI unit
\(\text{basis}\) power from flow and head, or shaft power entered –
\(Q\) flow m³/s
\(H\) total head m
\(\rho\) liquid density kg/m³
\(\eta_p\) pump efficiency –
\(P_{s,in}\) shaft power from the maker's data W
\(m_m\) motor margin –
\(P_{std}\) standard motor rating W
\(P_{m,min}\) minimum motor rating W
\(P_s\) power absorbed at the pump shaft W
\(P_h\) hydraulic power W
\(g\) standard gravity, 9.806 65 m/s²

Method and standards

Power definitions of ANSI/HI 1.6; standard ratings of IEC 60072-1 (up to 1 000 kW) and the ISO 3 R20 preferred numbers above. The default efficiency (68 %) and motor margin (18 %) are FireCAD design practice (owner, 2026-11-10); both are inputs.

Where it is used

  • Selecting feed, transfer and cooling water pump motors.
  • Checking motor size after an impeller change.
  • Specifying motors for purchase.

Common mistakes

  • Sizing on duty point power when the pump can run out further on its curve.
  • Adding margins twice.
  • Ignoring cold-water starting for hot-water pumps.

Assumptions and limits

  • Power at the duty point only; the end-of-curve power is not checked. For pumps that can run out to the end of their curve, check the power there too.
  • Direct drive; divide by the coupling or gearbox efficiency first if there is one.
  • Service factor, starting duty and ambient derating of the motor are not included.

References

  • ANSI/HI 1.6 (power definitions)
  • IEC 60072-1 (standard motor ratings)

Questions and answers

How do I select a motor for a pump?

Take the power absorbed at the duty, add the motor margin and choose the next standard rating. A pump for 30 m³/h at 45 m and 68 % absorbs 5.40 kW; with 18 % margin it needs 6.37 kW, so a 7.5 kW motor.

Why 18 %?

It is the FireCAD design-practice default for pump motors. Your specification, or the pump's end-of-curve power, may set a different margin; enter it.

Which standard ratings are used?

The IEC 60072-1 series (… 5.5, 7.5, 11, 15, 18.5, 22, 30, 37, 45, 55, 75, 90, 110 kW …) up to 1 000 kW, continued with the R20 preferred numbers above.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.