Worked example
Example: 8 bar(g), PDP 3 °C (refrigerant dryer). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Line pressure | 8.0000 bar g |
| Pressure dew point | 3.0000 °C |
| Atmospheric pressure | 1.0132 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Water vapour partial pressure in the line | 758.08 Pa |
| Dew or frost point after expansion to atmosphere | -21.983 °C |
| Water per kg of dry air | 0.52353 g/kg |
| Water per normal m³ of dry air | 0.67657 g/Nm³ |
Open this example in the calculator and change any input.
Formula
\(p_v = p_{sat}(T_{PDP})\)
\(p_{sat}(T_{ADP}) = p_v \frac{p_a}{p}\)
\(W = \frac{M_w}{M_a} \frac{p_v}{p - p_v}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p\) | Line pressure | Pa |
| \(T_{PDP}\) | Pressure dew point | K |
| \(p_a\) | Atmospheric pressure | Pa |
| \(p_v\) | Water vapour partial pressure in the line | Pa |
| \(T_{ADP}\) | Dew or frost point after expansion to atmosphere | K |
| \(W\) | Water per kg of dry air | kg/kg |
| \(c_w\) | Water per normal m³ of dry air | kg/m³ |
| \(p_{sat}\) | Saturation pressure over water or ice | Pa |
| \(M_w / M_a\) | Molar mass ratio water to dry air (0.622) | - |
Method and standards
Water vapour keeps its mole fraction when air expands, so its partial pressure falls in proportion to total pressure. Saturation is over liquid water (IAPWS-IF97) above 0.01 °C and over ice (IAPWS R14-08) below.
Where it is used
- Comparing dryers rated on different bases.
- Choosing a dryer for an ISO 8573-1 class.
- Checking whether lines outdoors can freeze.
Common mistakes
- Comparing a pressure dew point with an atmospheric one.
- Entering gauge pressure as absolute.
- Using dew point over water below 0 °C.
Assumptions and limits
- Ideal gas, no enhancement factor (at 10 bar and above the water content is under-estimated by roughly half a per cent).
- A line pressure entered as gauge is turned into absolute with the standard atmosphere; at altitude enter it as absolute (a note appears when p_a differs from 1.01325 bar).
- Dew point between −100 °C and 100 °C.
References
- IAPWS-IF97 saturation over water
- IAPWS R14-08(2011) sublimation pressure over ice
- ISO 8573-1 dew point classes (definitions)
Questions and answers
What is a 3 °C pressure dew point at 8 bar(g) in atmospheric terms?
The vapour pressure 758 Pa expands to 85 Pa at 1 atm, a frost point of −22 °C.
Why does it matter which one a dryer states?
A refrigerant dryer's 3 °C PDP and a desiccant dryer's −40 °C PDP look close in ADP terms, but the water content differs by a factor of fifty.
Is the dew point over ice or water?
Below 0 °C this page uses ice (a frost point), as hygrometers and ISO 8573 do.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.