FireCADCalc

Compressed Air Leak Flow and Cost

Air lost through a leak of a given hole size at line pressure, as free air delivery, compressor power, energy and cost per year (choked nozzle flow).

Process steam and utilitiesRefinery and petrochemicalChemical and fertiliserAir compressor and receiver

Inputs

Examples: 3 mm hole at 7 bar g1 mm hole at 6 bar g6 mm open fitting at 7 bar g, Cd 0.9

About 0.6–0.65 for a sharp-edged hole or crack; nearer 0.9 for a rounded fitting.
From the compressor data sheet or a plant energy audit; about 6–7 kW per m³/min at 7 bar g for a good screw compressor.

Results

Leak as free air2.4590m³/min
Leak mass flow169.01kg/h
Compressor power wasted15.983kW
Energy wasted per year127,866kWh
Cost per year (your currency)1,022,929
Choked flow (1 = yes)1.0000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 3 mm hole at 7 bar g. The inputs, in the units selected above:

InputValue
Hole diameter3.0000 mm
Line pressure7.0000 bar g
Air temperature in the line30.000 °C
Discharge coefficient of the hole65.000 %
Isentropic exponent of air1.4000 -
Atmospheric pressure (absolute)101.33 kPa
Compressor inlet temperature30.000 °C
Compressor specific power (kW per m³/min of FAD)6.5000 -
Hours under pressure per year8,000.0 h
Energy price per kWh (your currency)8.0000 -

Applying the formula below gives:

ResultValue
Leak as free air0.44036 m³/min
Leak mass flow30.766 kg/h
Compressor power wasted2.8624 kW
Energy wasted per year22,899 kWh
Cost per year (your currency)183,191
Choked flow (1 = yes)1.0000

Open this example in the calculator and change any input.

Formula

\(\rho_0 = \frac{p_0 M}{R T_0} \qquad \dot m = C_d A \sqrt{k\,p_0\,\rho_0}\left(\frac{2}{k+1}\right)^{\frac{k+1}{2(k-1)}} \text{ (choked)}\)

\(\dot m = C_d A \sqrt{\frac{2k}{k-1}\,p_0\rho_0\left[r^{2/k} - r^{(k+1)/k}\right]},\ r = \frac{p_a}{p_0}\ \text{(not choked)}\) \(\dot V_a = \frac{\dot m}{\rho_a} \qquad P = \dot V_a\,SP \qquad E = P\,t_y \qquad C = E\,c_e\)

Variables

Symbol Meaning SI unit
\(d\) hole diameter m
\(p_0\) line pressure Pa
\(T_0\) line temperature K
\(C_d\) discharge coefficient –
\(k\) isentropic exponent –
\(p_a\) atmospheric pressure Pa
\(T_a\) compressor inlet temperature K
\(SP\) specific power (P = V̇_a SP, with V̇_a in m³/min and SP in kW per m³/min) kW per m³/min
\(t_y\) hours per year s
\(c_e\) energy price currency/kWh
\(\dot V_a\) leak as free air m³/s
\(\dot m\) mass flow kg/s
\(P\) power wasted W
\(E\) energy per year J
\(C\) cost per year currency
\(\text{choked}\) choked flow flag –
\(r\) pressure ratio p_a/p_0 –
\(A\) hole area m²
\(\rho_0, \rho_a\) line and inlet air density kg/m³

Method and standards

Isentropic nozzle flow of an ideal gas (dry air of the PTC 4 composition), choked below the critical pressure ratio, else the subsonic form.

Where it is used

  • Leak surveys and tagging.
  • Justifying leak repair programmes.
  • Compressed-air energy audits.

Common mistakes

  • Using Cd of 1 for ragged holes.
  • Counting hours when the system is depressurised.
  • Forgetting that leaks also force extra compressors to run.

Assumptions and limits

  • Dry air; round hole; no pipe friction upstream.
  • A line pressure entered as gauge is turned into absolute with the standard atmosphere, not the site p_a; at altitude enter it as absolute (a note appears when p_a differs from 1.01325 bar).

References

  • Isentropic nozzle flow of an ideal gas

Questions and answers

What does a 3 mm leak at 7 bar g cost?

About 0.44 m³/min of free air, 2.9 kW of compressor power and 22 900 kWh a year at 8000 h: 183 000 a year at 8 per kWh.

Why is the flow choked?

Above about 0.9 bar g the leak reaches sonic speed in the hole; flow then rises in step with line pressure.

Which specific power?

Your compressor's kW per m³/min from the data sheet or an audit.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.