Wrong Thermocouple Type Reading Error

Temperature an instrument shows when a thermocouple of one type is read as another type (for example J read as K), from the NIST ITS-90 reference functions.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Type J read as K at 300 °CType K read as J at 500 °CType T read as K at 100 °C

Results

Cold junction taken at 0 °C. A real instrument compensates with the set type's function at its terminal temperature, so the shown value shifts by the difference between the two types' EMF at the terminals (a few kelvin for common pairs near room temperature).

EMF produced by the fitted thermocouple (cold junction 0 °C)4.2785mV
Temperature shown by the instrument104.41°C
Error (shown − true)4.4102K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Type J read as K at 300 °C. The inputs, in the units selected above:

InputValue
Thermocouple actually fittedType J (Iron / Constantan)
Type the instrument is set forType K (Chromel / Alumel)
True temperature at the hot junction300.00 °C

Applying the formula below gives:

ResultValue
EMF produced by the fitted thermocouple (cold junction 0 °C)16.327 mV
Temperature shown by the instrument398.34 °C
Error (shown − true)98.344 K

Open this example in the calculator and change any input.

Formula

\(T_{ind} = E_{set}^{-1}\big(E_{act}(T)\big)\)

Variables

Symbol Meaning SI unit
\(\text{sensor}\) Thermocouple actually fitted -
\(\text{set}\) Type the instrument is set for -
\(T\) True temperature at the hot junction K
\(E\) EMF produced by the fitted thermocouple (cold junction 0 °C) V
\(T_{ind}\) Temperature shown by the instrument K
\(\Delta T\) Error (shown − true) K

Method and standards

Forward NIST function of the fitted type, inverse function of the set type.

Where it is used

  • Commissioning and troubleshooting temperature loops.
  • Instrument technician training.

Common mistakes

  • Mixed extension cables.
  • Assuming colour codes match between standards.

Assumptions and limits

  • A real instrument adds E_set(T_terminal) for cold-junction compensation while the fitted sensor delivers E_act(T) − E_act(T_terminal); the shown value then differs from this 0 °C result by roughly the mismatch of the two types' EMF at terminal temperature.

  • Cold junction at 0 °C.

References

  • NIST ITS-90 thermocouple reference functions (NIST Monograph 175)

Questions and answers

What does a type K instrument show for a type J thermocouple at 300 °C?

The J produces 16.33 mV, which a K input reads as about 398 °C: nearly 100 K high.

How to spot it in the field?

Readings drift further from a reference thermometer as the temperature rises.

Does the extension cable matter?

Yes; it must match the sensor type too.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.