Worked example
Example: Type J read as K at 300 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Thermocouple actually fitted | Type J (Iron / Constantan) |
| Type the instrument is set for | Type K (Chromel / Alumel) |
| True temperature at the hot junction | 300.00 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| EMF produced by the fitted thermocouple (cold junction 0 °C) | 16.327 mV |
| Temperature shown by the instrument | 398.34 °C |
| Error (shown − true) | 98.344 K |
Open this example in the calculator and change any input.
Formula
\(T_{ind} = E_{set}^{-1}\big(E_{act}(T)\big)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{sensor}\) | Thermocouple actually fitted | - |
| \(\text{set}\) | Type the instrument is set for | - |
| \(T\) | True temperature at the hot junction | K |
| \(E\) | EMF produced by the fitted thermocouple (cold junction 0 °C) | V |
| \(T_{ind}\) | Temperature shown by the instrument | K |
| \(\Delta T\) | Error (shown − true) | K |
Method and standards
Forward NIST function of the fitted type, inverse function of the set type.
Where it is used
- Commissioning and troubleshooting temperature loops.
- Instrument technician training.
Common mistakes
- Mixed extension cables.
- Assuming colour codes match between standards.
Assumptions and limits
A real instrument adds E_set(T_terminal) for cold-junction compensation while the fitted sensor delivers E_act(T) − E_act(T_terminal); the shown value then differs from this 0 °C result by roughly the mismatch of the two types' EMF at terminal temperature.
Cold junction at 0 °C.
References
- NIST ITS-90 thermocouple reference functions (NIST Monograph 175)
Questions and answers
What does a type K instrument show for a type J thermocouple at 300 °C?
The J produces 16.33 mV, which a K input reads as about 398 °C: nearly 100 K high.
How to spot it in the field?
Readings drift further from a reference thermometer as the temperature rises.
Does the extension cable matter?
Yes; it must match the sensor type too.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.