Thermocouple mV from Temperature (Types B, E, J, K, N, R, S, T)

Thermocouple EMF in mV for a hot-junction and a cold-junction temperature, by the NIST ITS-90 reference functions, with the sensitivity in µV/°C.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserBoiler

Inputs

Examples: Type K at 400 °C, cold junction 25 °CType J at 300 °C, cold junction 30 °CType S at 1 000 °C, cold junction 25 °C

The temperature at the instrument terminals, where the thermocouple or its compensating cable ends. 0 °C gives the table value.

Results

EMF at the instrument terminals14.791mV
EMF with the cold junction at 0 °C (table value)16.327mV
EMF of the cold junction temperature (vs 0 °C)1.5367mV
Sensitivity at the hot junction55.355µV/K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Type K at 400 °C, cold junction 25 °C. The inputs, in the units selected above:

InputValue
Thermocouple typeType K (Chromel / Alumel)
Measuring (hot) junction temperature400.00 °C
Reference (cold) junction temperature25.000 °C

Applying the formula below gives:

ResultValue
EMF at the instrument terminals15.397 mV
EMF with the cold junction at 0 °C (table value)16.397 mV
EMF of the cold junction temperature (vs 0 °C)1.0002 mV
Sensitivity at the hot junction42.241 µV/K

Open this example in the calculator and change any input.

Formula

\(E = E(T) - E(T_{ref})\)

\(E(t) = \sum_{i=0}^{n} c_i\, t^{i} \;\; \left(+\, a_0\, e^{a_1 (t - a_2)^2}\ \text{for type K above 0 °C}\right)\)

\(S = \frac{dE}{dT}\)

Variables

Symbol Meaning SI unit
\(\text{type}\) thermocouple type (letter designation) -
\(T\) measuring (hot) junction temperature K
\(T_{ref}\) reference (cold) junction temperature K
\(E\) EMF at the instrument terminals V
\(E(T)\) EMF with the cold junction at 0 °C (table value) V
\(E(T_{ref})\) EMF corresponding to the cold junction temperature V
\(S\) sensitivity (Seebeck coefficient of the pair) at T V/K
\(t\) temperature in °C used inside the reference function °C
\(c_i, a_0, a_1, a_2\) NIST reference-function coefficients for each type and subrange mV, °C

Method and standards

The EMF comes from the ITS-90 thermocouple reference functions published by NIST (Monograph 175, Standard Reference Database 60), the same functions on which IEC 60584-1 and ASTM E230 tables are based. Each type has one to three temperature subranges with its own polynomial; type K above 0 °C adds an exponential term. The coefficients are read from NIST's published files, and the result is checked against every point of NIST's printed tables. The sensitivity is the exact derivative of the function.

Where it is used

  • Checking a thermocouple input card or transmitter with a mV source.
  • Finding what a temperature should read at the panel when the terminals are warm.
  • Comparing thermocouple types for resolution at the working temperature.

Common mistakes

  • Simulating a temperature with the table mV while the terminals are not at 0 °C: subtract the cold-junction EMF.
  • Using the wrong type: a type J table on a type K sensor reads far off at high temperature.
  • Treating the sensitivity as constant over a wide range; the curve is not straight, especially for B, R, S and below 0 °C.

Assumptions and limits

  • Reference functions for standard thermocouple wire; real sensors carry the tolerance class of their wire (not included).
  • Ranges: B 0–1 820 °C, E −270–1 000 °C, J −210–1 200 °C, K −270–1 372 °C, N −270–1 300 °C, R and S −50–1 768.1 °C, T −270–400 °C.
  • Extension and compensating cables are assumed to match the thermocouple up to the terminals.

References

  • NIST Monograph 175 / SRD 60 ITS-90 reference functions (as adopted in IEC 60584-1 and ASTM E230)

Questions and answers

What mV does a type K thermocouple give at 400 °C?

16.397 mV with the cold junction at 0 °C. With the instrument terminals at 25 °C the meter reads 15.397 mV, because 25 °C itself is worth 1.000 mV.

How sensitive is a type K thermocouple?

About 41–42 µV per °C over most of its range; type J about 55 µV/°C at 300 °C; type S only about 12 µV/°C at 1 000 °C.

Why does the cold junction matter?

A thermocouple measures the difference between its two junctions. The EMF at the terminals is E(T) − E(T_ref), so the terminal temperature must be known or compensated.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.