FireCADCalc

Thermistor Resistance and Temperature (β Equation)

Resistance of an NTC thermistor at a temperature from R25 and β, and the temperature from a measured resistance, with the sensitivity per kelvin.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 10 k, beta 3 950 at 50 °C; 6 kΩ measured100 k, beta 4 250 at 0 °C; 250 kΩ2.2 k, beta 3 500 at 80 °C; 500 Ω

Results

The β equation fits a limited range (typically ±50 K around the reference); use Steinhart–Hart for wide ranges. Sensitivity is per kelvin.

Resistance at T368,639Ω
Temperature at the measured resistance6.9923°C
Sensitivity at T, (1/R) dR/dT = −β/T² (per kelvin)-0.0569621/K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 k, beta 3 950 at 50 °C; 6 kΩ measured. The inputs, in the units selected above:

InputValue
Resistance at the reference temperature10,000 Ω
Reference temperature25.000 °C
β constant (K)3,950.0 -
Temperature (to find R)50.000 °C
Measured resistance (to find T)6,000.0 Ω

Applying the formula below gives:

ResultValue
Resistance at T3,588.2 Ω
Temperature at the measured resistance36.957 °C
Sensitivity at T, (1/R) dR/dT = −β/T² (per kelvin)-0.037826 1/K

Open this example in the calculator and change any input.

Formula

\(R_T = R_0\, e^{\beta(1/T - 1/T_0)}, \quad \frac1T = \frac{1}{T_0} + \frac{1}{\beta}\ln\frac{R}{R_0}\)

Variables

Symbol Meaning SI unit
\(R_0\) Resistance at the reference temperature Ω
\(T_0\) Reference temperature K
\(\beta\) β constant (K) -
\(T\) Temperature (to find R) K
\(R_m\) Measured resistance (to find T) Ω
\(R_T\) Resistance at T Ω
\(T_R\) Temperature at the measured resistance K
\(\alpha\) Sensitivity at T, (1/R) dR/dT = −β/T² (per kelvin) 1/K

Method and standards

Two-parameter NTC model.

Where it is used

  • HVAC and appliance sensors.
  • Motor winding protection.

Common mistakes

  • Using °C in the exponent.
  • Using β outside its fitted range.

Assumptions and limits

  • NTC thermistor.

References

  • NTC β model R = R₀ exp[β (1/T − 1/T₀)]

Questions and answers

What is a 10 k, β 3950 thermistor at 50 °C?

3588 Ω.

What temperature is 6 kΩ?

37.0 °C.

Why so sensitive?

About −4 % per kelvin near room temperature, ten times an RTD.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.