Pt100 / Pt1000 RTD Resistance–Temperature Calculator

Resistance of a Pt100 or Pt1000 platinum RTD at a temperature, and the temperature for a measured resistance, by the IEC 60751 Callendar–Van Dusen equation.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserBoiler

Inputs

Examples: Pt100 at 200 °C; reading 138.51 ΩPt100 at -50 °C; reading 80.31 ΩPt1000 at 350 °C; reading 2000 Ω

Results

Lead resistance adds to a 2-wire reading (about 2.6 °C per ohm for Pt100); use 3- or 4-wire connection.

Resistance at the temperature2,297.2Ω
Temperature for the measured resistance266.35°C

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Pt100 at 200 °C; reading 138.51 Ω. The inputs, in the units selected above:

InputValue
Resistance at 0 °C (100 for Pt100, 1000 for Pt1000)100.00 Ω
Temperature200.00 °C
Measured resistance138.51 Ω

Applying the formula below gives:

ResultValue
Resistance at the temperature175.86 Ω
Temperature for the measured resistance100.01 °C

Open this example in the calculator and change any input.

Formula

\(R(t) = R_0\left[1 + A t + B t^2 + C (t - 100)\,t^3\right] \quad (C = 0\ \text{for}\ t \ge 0\ ^\circ\mathrm{C})\)

Variables

Symbol Meaning SI unit
\(R_0\) resistance at 0 °C Ω
\(T\) temperature K
\(R_m\) measured resistance Ω
\(R_T\) resistance at T Ω
\(T_m\) temperature for R_m K
\(t\) temperature in °C °C
\(A, B, C\) IEC 60751 coefficients: 3.9083×10⁻³, −5.775×10⁻⁷, −4.183×10⁻¹² 1/°C, 1/°C², 1/°C⁴

Method and standards

IEC 60751 Callendar–Van Dusen equation for industrial platinum resistance thermometers (α = 0.00385); the inverse is solved numerically.

Where it is used

  • Checking RTD readings with a multimeter.
  • Configuring transmitters.
  • Troubleshooting temperature loops.

Common mistakes

  • Using Pt100 values for Pt1000 sensors.
  • Ignoring lead resistance in 2-wire circuits.
  • Using the formula outside −200 to 850 °C.

Assumptions and limits

  • IEC 60751 standard curve; sensor tolerance class not included.
  • The two directions are independent: a measured resistance outside the −200 °C to 850 °C range leaves out only its temperature, with a note.

References

  • IEC 60751 Callendar–Van Dusen coefficients A
  • B
  • C

Questions and answers

What resistance does a Pt100 have at 200 °C?

175.86 Ω. A Pt100 reading 138.51 Ω is at 100.0 °C.

Why does the formula change below 0 °C?

IEC 60751 adds the C term only below 0 °C to fit the platinum curve at low temperatures.

How much error do the leads add?

A Pt100 changes about 0.385 Ω per K, so each ohm of lead resistance reads about 2.6 K high in a 2-wire connection; 3- or 4-wire connections cancel it.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.