FireCADCalc

Intrinsic Safety: Maximum Cable Length by Entity Parameters

Maximum cable length of an intrinsically safe loop from the barrier's allowed capacitance and inductance, the device's internal values and the cable's.

Thermal power plantProcess steam and utilitiesRefinery and petrochemical

Inputs

Examples: Illustrative IIC barrierIIB barrier, long runInductance-limited high current

Accepted: 0.001 to 1,000 µF
Accepted: 0.001 to 1,000 mH
Accepted: 0 to 1,000 µF
Accepted: 0 to 1,000 mH
Accepted: 10 to 1,000 nF/km
Accepted: 0.01 to 5 mH/km

Results

Entity check: C_i + C_cℓ ≤ C_o and L_i + L_cℓ ≤ L_o, so ℓ = min[(C_o − C_i)/C_c, (L_o − L_i)/L_c]. Where both C_i and L_i exceed 1 % of the allowed values, stricter combined rules apply; the cable's L/R ratio may be used instead of its inductance if the barrier states an L/R limit. Voltage, current and power must also match (U_i ≥ U_o, etc.).

Length limit by capacitance5.3333km
Length limit by inductance14.975km
Maximum cable length5.3333km

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative IIC barrier. The inputs, in the units selected above:

InputValue
Barrier maximum external capacitance0.083000 µF
Barrier maximum external inductance3.0000 mH
Device internal capacitance0.005000 µF
Device internal inductance0.010000 mH
Cable capacitance per km100.00 nF/km
Cable inductance per km0.70000 mH/km

Applying the formula below gives:

ResultValue
Length limit by capacitance0.78000 km
Length limit by inductance4.2714 km
Maximum cable length0.78000 km

Open this example in the calculator and change any input.

Formula

\(\ell_{max} = \min\left(\frac{C_o - C_i}{C_c}, \frac{L_o - L_i}{L_c}\right)\)

Variables

Symbol Meaning SI unit
\(C_o\) Barrier maximum external capacitance F
\(L_o\) Barrier maximum external inductance H
\(C_i\) Device internal capacitance F
\(L_i\) Device internal inductance H
\(C_c\) Cable capacitance per km F/m
\(L_c\) Cable inductance per km H/m
\(\ell_C\) Length limit by capacitance m
\(\ell_L\) Length limit by inductance m
\(\ell_{max}\) Maximum cable length m

Method and standards

IS cable length.

Where it is used

  • Hazardous-area loop design and inspection.
  • Checking replacement cables.

Common mistakes

  • Forgetting the device's internal values.
  • Using the cable's loop rather than per-conductor values inconsistently.

Assumptions and limits

  • Simple entity check; one barrier and one device.

References

  • Entity concept for intrinsically safe loops
  • Intrinsic safety entity concept: cable parameters against source Co and Lo

Questions and answers

Why does cable length matter for intrinsic safety?

Cable capacitance and inductance store energy that could be released as a spark; long cables store more.

Which limit usually governs?

Capacitance for high-voltage barriers (Group IIC especially), inductance for high-current circuits.

What do the defaults represent?

An illustrative barrier allowing 83 nF and 3 mH, a device with 5 nF and 10 µH, and cable of 100 nF/km and 0.7 mH/km.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.