FireCADCalc

Encoder Pulse Frequency and Speed Measurement Resolution

Pulse frequency of an incremental encoder at a speed, counts per gate time, speed resolution by frequency counting and by period timing, and angular resolution.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 1024 PPR x4 at 1500 rpmLow speed 10 rpm, 2048 PPRSimple 60-tooth wheel x1

Accepted: 1 to 1,000,000
Accepted: 1 to 4
Accepted: 0.6 to 60,000 rpm
Accepted: 0.1 to 10,000 ms
Accepted: 0.001 to 1,000 MHz

Results

Frequency method: one count in the gate time is 1/(PPR·k·T_g) rev/s, good at high speed. Period method: timing one edge interval with a clock, relative resolution f/f_clk, good at low speed. Many drives switch between the two.

Pulse (count) frequency3.0000kHz
Counts per gate300.00
Resolution, frequency method10.000rpm
Relative resolution, period method0.30000%
Angular resolution6.0000°

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 1024 PPR x4 at 1500 rpm. The inputs, in the units selected above:

InputValue
Pulses per revolution1,024.0 -
Edge multiplication (1, 2 or 4)4.0000 -
Shaft speed1,500.0 rpm
Gate (counting) time10.000 ms
Timer clock for period method10.000 MHz

Applying the formula below gives:

ResultValue
Pulse (count) frequency102.40 kHz
Counts per gate1,024.0
Resolution, frequency method1.4648 rpm
Relative resolution, period method1.0240 %
Angular resolution0.087891 °

Open this example in the calculator and change any input.

Formula

\(f = n\cdot PPR\cdot k, \quad \Delta n_f = \frac{1}{PPR\cdot k\cdot T_g}, \quad \frac{\Delta n_p}{n} = \frac{f}{f_{clk}}\)

Variables

Symbol Meaning SI unit
\(PPR\) Pulses per revolution -
\(k\) Edge multiplication (1, 2 or 4) -
\(n\) Shaft speed 1/s
\(T_g\) Gate (counting) time s
\(f_{clk}\) Timer clock for period method 1/s
\(f\) Pulse (count) frequency 1/s
\(N_g\) Counts per gate -
\(\Delta n_f\) Resolution, frequency method 1/s
\(\Delta n_p/n\) Relative resolution, period method -
\(\Delta\theta\) Angular resolution rad

Method and standards

Encoder resolution.

Where it is used

  • Drive and motion control feedback.
  • Conveyor and roll speed measurement.

Common mistakes

  • Exceeding the input card's maximum frequency.
  • Using too short a gate at low speed.

Assumptions and limits

  • Ideal encoder without jitter.

References

  • Incremental encoder speed measurement
  • Liptak
  • Instrument Engineers' Handbook
  • Vol. 1 and 2 (CRC Press)

Questions and answers

Why use quadrature ×4?

Counting both edges of both channels quadruples resolution and gives direction.

Which method suits low speed?

Period timing: at low speed few pulses arrive in a gate, so frequency counting is coarse.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.