Worked example
Example: PRV 10 t/h, 10.5 to 4 bar(a), saturated (choked). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Steam flow | 10,000 kg/h |
| Upstream pressure (absolute) | 10.500 bar |
| Downstream pressure (absolute) | 4.0000 bar |
| Steam condition at the inlet | Dry saturated |
| Steam temperature (superheated only) | 250.00 °C |
| Specific heat ratio of steam | 1.1350 - |
| Pressure differential ratio factor of the valve | 0.72000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Flow coefficient Kv | 82.582 |
| Flow coefficient Cv | 95.590 |
| Pressure drop ratio Δp/p₁ | 0.61905 |
| Choked limit of the ratio | 0.58371 |
| Expansion factor | 0.66667 |
| Steam density at the inlet | 5.3907 kg/m³ |
| Choked (1 = yes) | 1.0000 |
Open this example in the calculator and change any input.
Formula
\(x = \frac{p_1 - p_2}{p_1} \qquad F_\gamma = \frac{\gamma}{1.4} \qquad x_s = \min(x,\ F_\gamma x_T) \qquad Y = 1 - \frac{x_s}{3\,F_\gamma\,x_T}\)
\(K_v = \frac{W}{31.6\;Y\sqrt{x_s\,p_1\,\rho_1}} \qquad C_v = \frac{W}{27.3\;Y\sqrt{x_s\,p_1\,\rho_1}} \qquad (W\ \text{in kg/h},\ p_1\ \text{in bar},\ \rho_1\ \text{in kg/m}^3)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(W\) | steam flow | kg/s |
| \(p_1\) | upstream pressure, absolute | Pa |
| \(p_2\) | downstream pressure, absolute | Pa |
| \(\text{state}\) | dry saturated or superheated steam | – |
| \(T_s\) | steam temperature (superheated) | K |
| \(\gamma\) | specific heat ratio of steam | – |
| \(x_T\) | pressure differential ratio factor of the valve | – |
| \(K_v\) | flow coefficient Kv | – |
| \(C_v\) | flow coefficient Cv | – |
| \(x\) | pressure drop ratio | – |
| \(F_\gamma x_T\) | choked limit of the ratio | – |
| \(Y\) | expansion factor | – |
| \(\rho_1\) | steam density at the inlet | kg/m³ |
| \(\text{choked}\) | 1 when the flow is choked | – |
| \(x_s\) | ratio used for sizing | – |
Method and standards
IEC 60534-2-1:2011 for compressible fluids without attached fittings, with the numerical constants N₆ of its Table 1 (31.6 for Kv and 27.3 for Cv with kg/h, bar and kg/m³). Steam density from FireCAD's IAPWS-IF97.
Where it is used
- Sizing PRDS and process steam control valves.
- Checking valves on steam headers.
- Specifying valves for purchase.
Common mistakes
- Ignoring choked flow at high pressure ratios.
- Using gauge pressures in the sizing equation.
- Forgetting the outlet velocity and noise.
Assumptions and limits
- No reducers on the valve (F_P = 1).
- x_T from the maker at the operating opening.
- γ is your entry and is not checked against the steam state: about 1.3 for superheated and 1.135 for dry saturated steam.
- Noise and outlet velocity are not checked; choked steam valves usually need low-noise trim.
References
- IEC 60534-2-1:2011 (compressible fluids)
- ANSI/ISA-75.01.01
- IAPWS R7-97(2012) IF97
Questions and answers
How do I size a steam control valve?
Kv = W/(31.6·Y·√(x·p₁·ρ₁)) with W in kg/h, p₁ in bar and ρ₁ in kg/m³. A valve reducing 10 t/h of saturated steam from 10.5 to 4 bar(a) needs Kv 82.6 (Cv 95.6) and is choked.
What does choked mean for a steam valve?
When the pressure drop ratio x = Δp/p₁ exceeds F_γ·x_T, the flow no longer increases with a lower outlet pressure. The valve is then sized on the limit, and noise is high.
Where do x_T and γ come from?
x_T from the valve maker for the valve type; γ is about 1.3 for superheated and 1.135 for saturated steam.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.