Worked example
Example: 12 L actuator to 3 bar(a), 6 m³/h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Actuator swept volume plus dead volume | 12.000 L |
| Starting pressure (absolute) | 1.0132 bar |
| End pressure (absolute) | 3.0000 bar |
| Air delivery (free air, at 1.01325 bar) | 6.0000 m³/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Free air needed | 23.529 L |
| Stroke time | 14.118 s |
Open this example in the calculator and change any input.
Formula
\(V_n = V\frac{|p_2 - p_1|}{p_0}, \quad t = \frac{V_n}{\dot V_n}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Actuator swept volume plus dead volume | m³ |
| \(p_1\) | Starting pressure (absolute) | Pa |
| \(p_2\) | End pressure (absolute) | Pa |
| \(\dot V_n\) | Air delivery (free air, at 1.01325 bar) | m³/s |
| \(V_{n}\) | Free air needed | m³ |
| \(t\) | Stroke time | s |
Method and standards
Isothermal fill.
Where it is used
- Shut-down valve stroke checks.
- Booster selection.
Common mistakes
- Ignoring tubing volume.
- Using supply pressure instead of the actuator range.
Assumptions and limits
Isothermal fill at constant volume and constant average air delivery. Real filling is closer to adiabatic and the delivery falls as the actuator pressure approaches the supply, so real stroke times are longer; the 20–50 % allowance in the note is a rule of thumb, not a sourced figure. Time it on the valve where it matters (ESD valves).
Isothermal; average delivery.
References
- Isothermal mass balance of the actuator volume (definitions)
Questions and answers
Why are large actuators slow?
Their volume must be filled with air through small positioner ports; delivery, not the spring, usually limits speed.
What is a typical requirement?
Emergency shut-down valves often need closure in 2–10 s; control valves 5–30 s full stroke.
What do the defaults represent?
A 12 L actuator stroked from atmospheric to 3 bar(a) with 6 m³/h of free air.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.