Worked example
Example: 50 mm seat, 10 bar, 645 cm², 1.0 bar. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Shut-off pressure drop | 10.000 bar |
| Seat (port) diameter | 50.000 mm |
| Packing friction | 400.00 N |
| Seat load per mm of seat circumference (N/mm) | 20.000 - |
| Effective diaphragm area | 645.00 cm² |
| Bench-set pressure at the seating end | 1.0000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Unbalance (fluid) force | 1,963.5 N |
| Seat load | 3,141.6 N |
| Required thrust | 5,505.1 N |
| Available spring thrust at seating | 6,450.0 N |
| Thrust margin | 1.1716 |
Open this example in the calculator and change any input.
Formula
\(F_{req} = \Delta p_{so}\frac{\pi d_s^2}{4} + F_p + f_s\pi d_s, \quad F_{av} = p_bA_d\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\Delta p_{so}\) | Shut-off pressure drop | Pa |
| \(d_s\) | Seat (port) diameter | m |
| \(F_p\) | Packing friction | N |
| \(f_s\) | Seat load per mm of seat circumference (N/mm) | - |
| \(A_d\) | Effective diaphragm area | m² |
| \(p_b\) | Bench-set pressure at the seating end | Pa |
| \(F_{unb}\) | Unbalance (fluid) force | N |
| \(F_{seat}\) | Seat load | N |
| \(F_{req}\) | Required thrust | N |
| \(F_{av}\) | Available spring thrust at seating | N |
| \(F_{av}/F_{req}\) | Thrust margin | - |
Method and standards
Force balance.
Where it is used
- Actuator selection.
- Troubleshooting seat leakage.
Common mistakes
- Ignoring packing friction (graphite packing is high).
- Using supply instead of bench pressure.
Assumptions and limits
The page warns when the thrust margin is below 1 (the actuator cannot seat the plug).
Flow tending to open the plug is assumed; the stem area (which adds p₁ × stem area against closing) and flow-to-close arrangements (where the fluid helps closure but can slam the plug) are not modelled.
Unbalanced plug; spring-to-close.
References
- Force balance on an unbalanced globe valve plug and a spring–diaphragm actuator (Lipták, Instrument Engineers' Handbook, 4th ed. (CRC Press), vol. 2, control valve actuators)
Questions and answers
Why does the valve leak at shut-off?
Often because the actuator cannot push the plug hard enough against the full shut-off pressure plus friction.
What is bench set?
The air pressure range over which the actuator strokes on the bench with no process pressure; the seating end sets the spring force at closure.
What do the defaults represent?
A 50 mm seat closing against 10 bar with a 645 cm² diaphragm and 1.0 bar bench set at the seat.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.