Worked example
Example: Equal %, R 50, 50 % open, authority 0.3. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Inherent characteristic | Equal percentage |
| Valve travel (opening) | 50.000 % |
| Inherent rangeability (largest to least controllable flow) | 50.000 - |
| Valve authority (valve Δp fully open ÷ system Δp) | 30.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Inherent relative flow (at constant Δp) | 14.142 % |
| Installed relative flow (share of full-open flow) | 25.238 % |
| Installed gain | 0.94329 |
| Installed flow at the least controllable opening | 3.6498 % |
Open this example in the calculator and change any input.
Formula
\(\varphi = x \ \text{(linear)} \qquad \varphi = R^{\,x - 1}\ \text{(equal \%)} \qquad q = \frac{\varphi}{\sqrt{N + (1 - N)\varphi^2}} \qquad \frac{dq}{dx} = \frac{N}{[N + (1 - N)\varphi^2]^{3/2}}\,\frac{d\varphi}{dx} \qquad q_{min} = \frac{1/R}{\sqrt{N + (1 - N)/R^2}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{char}\) | inherent characteristic | – |
| \(x\) | travel | – |
| \(R\) | inherent rangeability | – |
| \(N\) | valve authority | – |
| \(\varphi\) | inherent relative flow | – |
| \(q\) | installed relative flow | – |
| \(dq/dx\) | installed gain | – |
| \(q_{min}\) | installed flow at the least controllable opening | – |
Method and standards
Ideal inherent characteristics with a valve in series with a fixed-resistance system of constant total pressure drop.
Where it is used
- Choosing valve trim.
- Explaining poor control at low or high load.
- Feedwater and spray control valves.
Common mistakes
- Ignoring authority.
- Oversized valves working near closed.
- Confusing inherent and installed rangeability.
Assumptions and limits
- Ideal characteristics; constant total system drop; turbulent flow.
- The least controllable inherent flow is 1/R of the full flow for either characteristic.
- The 0.25 authority warning is a common rule of thumb, not a standard limit.
References
- IEC 60534-2-4 (inherent characteristics)
Questions and answers
What flows through an equal-% valve at 50 % open with R 50 and authority 0.3?
Inherent 14.1 % of full flow; installed 25.2 %, with gain 0.94.
What is valve authority?
Valve pressure drop fully open divided by the total system drop; low authority distorts the characteristic toward quick-opening.
When to choose equal percentage?
When most of the system drop is outside the valve: its installed curve becomes nearly linear.