FireCADCalc

Control Valve Cv and Kv for Steam (IEC 60534)

Flow coefficient Kv and Cv of a control valve or pressure reducing valve on steam by IEC 60534-2-1, with the expansion factor and the choked-flow check.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserIAPWS-IF97 (water and steam)Desuperheater and PRDS

Inputs

Examples: PRV 10 t/h, 10.5 to 4 bar(a), saturated (choked)Steam control valve 20 t/h, 40 to 35 bar(a), 400 °CHeater valve 1 t/h, 4 to 3 bar(a), saturated

1.3 for superheated steam; 1.135 for dry saturated steam.
From the valve maker; about 0.7 for single-seat globe valves, 0.2–0.5 for ball and butterfly valves.

Results

The flow is choked: the pressure drop ratio exceeds F_γ·x_T, the coefficient is sized on the limit, and noise will be high; consider a low-noise trim or two stages.

Flow coefficient Kv82.582
Flow coefficient Cv95.590
Pressure drop ratio Δp/p₁0.61905
Choked limit of the ratio0.58371
Expansion factor0.66667
Steam density at the inlet5.3907kg/m³
Choked (1 = yes)1.0000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: PRV 10 t/h, 10.5 to 4 bar(a), saturated (choked). The inputs, in the units selected above:

InputValue
Steam flow10,000 kg/h
Upstream pressure (absolute)10.500 bar
Downstream pressure (absolute)4.0000 bar
Steam condition at the inletDry saturated
Steam temperature (superheated only)250.00 °C
Specific heat ratio of steam1.1350 -
Pressure differential ratio factor of the valve0.72000 -

Applying the formula below gives:

ResultValue
Flow coefficient Kv82.582
Flow coefficient Cv95.590
Pressure drop ratio Δp/p₁0.61905
Choked limit of the ratio0.58371
Expansion factor0.66667
Steam density at the inlet5.3907 kg/m³
Choked (1 = yes)1.0000

Open this example in the calculator and change any input.

Formula

\(x = \frac{p_1 - p_2}{p_1} \qquad F_\gamma = \frac{\gamma}{1.4} \qquad x_s = \min(x,\ F_\gamma x_T) \qquad Y = 1 - \frac{x_s}{3\,F_\gamma\,x_T}\)

\(K_v = \frac{W}{31.6\;Y\sqrt{x_s\,p_1\,\rho_1}} \qquad C_v = \frac{W}{27.3\;Y\sqrt{x_s\,p_1\,\rho_1}} \qquad (W\ \text{in kg/h},\ p_1\ \text{in bar},\ \rho_1\ \text{in kg/m}^3)\)

Variables

Symbol Meaning SI unit
\(W\) steam flow kg/s
\(p_1\) upstream pressure, absolute Pa
\(p_2\) downstream pressure, absolute Pa
\(\text{state}\) dry saturated or superheated steam –
\(T_s\) steam temperature (superheated) K
\(\gamma\) specific heat ratio of steam –
\(x_T\) pressure differential ratio factor of the valve –
\(K_v\) flow coefficient Kv –
\(C_v\) flow coefficient Cv –
\(x\) pressure drop ratio –
\(F_\gamma x_T\) choked limit of the ratio –
\(Y\) expansion factor –
\(\rho_1\) steam density at the inlet kg/m³
\(\text{choked}\) 1 when the flow is choked –
\(x_s\) ratio used for sizing –

Method and standards

IEC 60534-2-1:2011 for compressible fluids without attached fittings, with the numerical constants N₆ of its Table 1 (31.6 for Kv and 27.3 for Cv with kg/h, bar and kg/m³). Steam density from FireCAD's IAPWS-IF97.

Where it is used

  • Sizing PRDS and process steam control valves.
  • Checking valves on steam headers.
  • Specifying valves for purchase.

Common mistakes

  • Ignoring choked flow at high pressure ratios.
  • Using gauge pressures in the sizing equation.
  • Forgetting the outlet velocity and noise.

Assumptions and limits

  • No reducers on the valve (F_P = 1).
  • x_T from the maker at the operating opening.
  • γ is your entry and is not checked against the steam state: about 1.3 for superheated and 1.135 for dry saturated steam.
  • Noise and outlet velocity are not checked; choked steam valves usually need low-noise trim.

References

  • IEC 60534-2-1:2011 (compressible fluids)
  • ANSI/ISA-75.01.01
  • IAPWS R7-97(2012) IF97

Questions and answers

How do I size a steam control valve?

Kv = W/(31.6·Y·√(x·p₁·ρ₁)) with W in kg/h, p₁ in bar and ρ₁ in kg/m³. A valve reducing 10 t/h of saturated steam from 10.5 to 4 bar(a) needs Kv 82.6 (Cv 95.6) and is choked.

What does choked mean for a steam valve?

When the pressure drop ratio x = Δp/p₁ exceeds F_γ·x_T, the flow no longer increases with a lower outlet pressure. The valve is then sized on the limit, and noise is high.

Where do x_T and γ come from?

x_T from the valve maker for the valve type; γ is about 1.3 for superheated and 1.135 for saturated steam.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.