Refrigeration Superheat and Sub-Cooling from Readings

Evaporator superheat and condenser sub-cooling from measured suction and liquid line temperatures and the saturation temperatures read off the gauges.

Food, dairy and textileRefrigeration and air-conditioning mechanic examinations

Inputs

Examples: Normal readingsUndercharged

From the refrigerant's pressure–temperature chart; for a zeotropic blend (R407C, R404A …) use the dew-point temperature.
For a zeotropic blend use the bubble-point temperature.

Results

Superheat T_suc − T_evap20.000K
Sub-cooling T_cond − T_liq1.0000K
Condenser approach T_cond − T_a8.0000K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Normal readings. The inputs, in the units selected above:

InputValue
Suction line temperature (at the bulb)8.0000 °C
Evaporating (saturation) temperature from the suction gauge2.0000 °C
Liquid line temperature36.000 °C
Condensing (saturation) temperature from the discharge gauge42.000 °C
Air or water temperature entering the condenser30.000 °C

Applying the formula below gives:

ResultValue
Superheat T_suc − T_evap6.0000 K
Sub-cooling T_cond − T_liq6.0000 K
Condenser approach T_cond − T_a12.000 K

Open this example in the calculator and change any input.

Formula

\(SH = T_{suc} - T_{evap}, \quad SC = T_{cond} - T_{liq}\)

Variables

Symbol Meaning SI unit
\(T_{suc}\) Suction line temperature (at the bulb) K
\(T_{evap}\) Evaporating (saturation) temperature from the suction gauge K
\(T_{liq}\) Liquid line temperature K
\(T_{cond}\) Condensing (saturation) temperature from the discharge gauge K
\(T_a\) Air or water temperature entering the condenser K
\(SH\) Superheat T_suc − T_evap K
\(SC\) Sub-cooling T_cond − T_liq K
\(\Delta T_c\) Condenser approach T_cond − T_a K

Method and standards

Definitions.

Where it is used

  • Refrigeration and AC servicing.
  • Refrigeration mechanic examinations.

Common mistakes

  • Using gauge pressure without the P–T chart.
  • Bulb location away from the evaporator outlet.

Assumptions and limits

  • Steady running.
  • Zeotropic blends (R407C, R404A and other 400-series mixtures) have a temperature glide: superheat is measured from the dew-point temperature at suction pressure and sub-cooling from the bubble-point temperature at liquid pressure. Pure refrigerants and azeotropes have one saturation temperature.

References

  • Definitions: superheat = suction temperature − saturation temperature; sub-cooling = condensing temperature − liquid temperature

Questions and answers

Suction 8 °C at 2 °C saturation, liquid 36 °C at 42 °C condensing?

Superheat 6 K, sub-cooling 6 K.

High superheat?

Often undercharge or a starving expansion valve.

High sub-cooling?

Often overcharge or a restriction after the condenser.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.