Worked example
Example: Normal readings. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Suction line temperature (at the bulb) | 8.0000 °C |
| Evaporating (saturation) temperature from the suction gauge | 2.0000 °C |
| Liquid line temperature | 36.000 °C |
| Condensing (saturation) temperature from the discharge gauge | 42.000 °C |
| Air or water temperature entering the condenser | 30.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Superheat T_suc − T_evap | 6.0000 K |
| Sub-cooling T_cond − T_liq | 6.0000 K |
| Condenser approach T_cond − T_a | 12.000 K |
Open this example in the calculator and change any input.
Formula
\(SH = T_{suc} - T_{evap}, \quad SC = T_{cond} - T_{liq}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_{suc}\) | Suction line temperature (at the bulb) | K |
| \(T_{evap}\) | Evaporating (saturation) temperature from the suction gauge | K |
| \(T_{liq}\) | Liquid line temperature | K |
| \(T_{cond}\) | Condensing (saturation) temperature from the discharge gauge | K |
| \(T_a\) | Air or water temperature entering the condenser | K |
| \(SH\) | Superheat T_suc − T_evap | K |
| \(SC\) | Sub-cooling T_cond − T_liq | K |
| \(\Delta T_c\) | Condenser approach T_cond − T_a | K |
Method and standards
Definitions.
Where it is used
- Refrigeration and AC servicing.
- Refrigeration mechanic examinations.
Common mistakes
- Using gauge pressure without the P–T chart.
- Bulb location away from the evaporator outlet.
Assumptions and limits
- Steady running.
- Zeotropic blends (R407C, R404A and other 400-series mixtures) have a temperature glide: superheat is measured from the dew-point temperature at suction pressure and sub-cooling from the bubble-point temperature at liquid pressure. Pure refrigerants and azeotropes have one saturation temperature.
References
- Definitions: superheat = suction temperature − saturation temperature; sub-cooling = condensing temperature − liquid temperature
Questions and answers
Suction 8 °C at 2 °C saturation, liquid 36 °C at 42 °C condensing?
Superheat 6 K, sub-cooling 6 K.
High superheat?
Often undercharge or a starving expansion valve.
High sub-cooling?
Often overcharge or a restriction after the condenser.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.