FireCADCalc

Carnot COP of a Refrigerator or Heat Pump

Ideal (Carnot) COP for cooling and for heating from evaporating and condensing temperatures, the least kW per TR, and the second-law efficiency of a real machine.

Food, dairy and textileAir conditioning and chillersRefrigeration and air-conditioning mechanic examinations

Inputs

Examples: Chiller: evaporating 5 °C, condensing 40 °C, COP 5.5Cold store: -25 °C / 35 °C, COP 2.0Heat pump: 0 °C / 50 °C, COP 3.2

Results

Carnot COP, cooling5.4630
Carnot COP, heating (heat pump)6.4630
Least power per ton of refrigeration (kW/TR)0.64376
Second-law efficiency of the machine58.576%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Chiller: evaporating 5 °C, condensing 40 °C, COP 5.5. The inputs, in the units selected above:

InputValue
Evaporating temperature5.0000 °C
Condensing temperature40.000 °C
Actual cooling COP of the machine5.5000 -

Applying the formula below gives:

ResultValue
Carnot COP, cooling7.9471
Carnot COP, heating (heat pump)8.9471
Least power per ton of refrigeration (kW/TR)0.44253
Second-law efficiency of the machine69.207 %

Open this example in the calculator and change any input.

Formula

\(COP_{R,C} = \frac{T_e}{T_c - T_e} \qquad COP_{HP,C} = \frac{T_c}{T_c - T_e} \qquad \text{kW/TR}_{min} = \frac{3.517}{COP_{R,C}} \qquad \eta_{II} = \frac{COP}{COP_{R,C}}\)

Variables

Symbol Meaning SI unit
\(T_e\) evaporating temperature K
\(T_c\) condensing temperature K
\(COP\) actual cooling COP –
\(COP_{R,C}\) Carnot cooling COP –
\(COP_{HP,C}\) Carnot heating COP –
\(\text{kW/TR}_{min}\) least power per TR kW/TR
\(\eta_{II}\) second-law efficiency –

Method and standards

Reversed Carnot cycle between two reservoirs at the evaporating and condensing temperatures.

Where it is used

  • Judging how good a chiller or heat pump is.
  • Effect of condenser water temperature on chiller power.
  • Heat pump feasibility.

Common mistakes

  • Using °C instead of kelvin.
  • Using water temperatures, which overstate the COP.
  • Expecting more than about 60–70 % of Carnot from real machines.

Assumptions and limits

  • Ideal reversible cycle; real cycles lose to compression, throttling and heat-exchanger approach.

References

  • Carnot cycle (classical thermodynamics)

Questions and answers

What is the Carnot COP between 5 °C and 40 °C?

7.95 for cooling and 8.95 for heating; a chiller with COP 5.5 reaches 69 % of the Carnot limit.

Why does lift matter so much?

COP falls as the condensing temperature rises above the evaporating one; every kelvin of lift costs about 2–3 % of power.

Which temperatures do I use?

Refrigerant evaporating and condensing temperatures, not the water temperatures.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.