Worked example
Example: Chiller: evaporating 5 °C, condensing 40 °C, COP 5.5. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Evaporating temperature | 5.0000 °C |
| Condensing temperature | 40.000 °C |
| Actual cooling COP of the machine | 5.5000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Carnot COP, cooling | 7.9471 |
| Carnot COP, heating (heat pump) | 8.9471 |
| Least power per ton of refrigeration (kW/TR) | 0.44253 |
| Second-law efficiency of the machine | 69.207 % |
Open this example in the calculator and change any input.
Formula
\(COP_{R,C} = \frac{T_e}{T_c - T_e} \qquad COP_{HP,C} = \frac{T_c}{T_c - T_e} \qquad \text{kW/TR}_{min} = \frac{3.517}{COP_{R,C}} \qquad \eta_{II} = \frac{COP}{COP_{R,C}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_e\) | evaporating temperature | K |
| \(T_c\) | condensing temperature | K |
| \(COP\) | actual cooling COP | – |
| \(COP_{R,C}\) | Carnot cooling COP | – |
| \(COP_{HP,C}\) | Carnot heating COP | – |
| \(\text{kW/TR}_{min}\) | least power per TR | kW/TR |
| \(\eta_{II}\) | second-law efficiency | – |
Method and standards
Reversed Carnot cycle between two reservoirs at the evaporating and condensing temperatures.
Where it is used
- Judging how good a chiller or heat pump is.
- Effect of condenser water temperature on chiller power.
- Heat pump feasibility.
Common mistakes
- Using °C instead of kelvin.
- Using water temperatures, which overstate the COP.
- Expecting more than about 60–70 % of Carnot from real machines.
Assumptions and limits
- Ideal reversible cycle; real cycles lose to compression, throttling and heat-exchanger approach.
References
- Carnot cycle (classical thermodynamics)
Questions and answers
What is the Carnot COP between 5 °C and 40 °C?
7.95 for cooling and 8.95 for heating; a chiller with COP 5.5 reaches 69 % of the Carnot limit.
Why does lift matter so much?
COP falls as the condensing temperature rises above the evaporating one; every kelvin of lift costs about 2–3 % of power.
Which temperatures do I use?
Refrigerant evaporating and condensing temperatures, not the water temperatures.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.