Worked example
Example: 20 t at 2 °C, illustrative f and g. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Product mass | 20.000 t |
| Storage temperature | 2.0000 °C |
| Respiration coefficient f | 5.6871e-04 - |
| Respiration exponent g | 2.5977 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Specific respiration heat (mW/kg) | 18.121 |
| Respiration heat load | 0.36241 kW |
| Heat per day | 31.312 MJ |
Open this example in the calculator and change any input.
Formula
\(q = \frac{10.7f}{3600}\left(\frac95t + 32\right)^g\ \ \mathrm{W/kg}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(m\) | Product mass | kg |
| \(t\) | Storage temperature | K |
| \(f\) | Respiration coefficient f | - |
| \(g\) | Respiration exponent g | - |
| \(q\) | Specific respiration heat (mW/kg) | - |
| \(Q\) | Respiration heat load | W |
| \(E_d\) | Heat per day | J |
Method and standards
Becker–Fricke correlation.
Where it is used
- Cold store refrigeration load.
- Ripening rooms and pack houses.
Common mistakes
- Using frozen-product data for fresh produce.
- Ignoring ripening rooms' higher rates.
Assumptions and limits
- Fresh produce; t in °C.
References
- Becker
- Misra and Fricke (1996)
- Int. J. Refrig. 19: 2 (respiration correlation); ASHRAE Handbook—Refrigeration (2018)
- ch. 19
Questions and answers
Why does stored produce make heat?
Fruits and vegetables are alive: they burn sugars with oxygen and release heat, CO₂ and moisture.
Why store cold?
Respiration (and so ripening and weight loss) slows sharply as temperature falls.
What do the defaults represent?
20 t of a hard fruit at 2 °C with illustrative respiration coefficients; enter the commodity's own f and g.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.