Liquid Line Subcooling Needed Against Lift and Pressure Drop

Liquid line pressure loss from friction and lift, the subcooling needed to stop flash gas at the expansion valve, and the margin over actual.

Process steam and utilitiesDistillery and ethanolChemical and fertiliserFood, dairy and textile

Inputs

Examples: 8 m riser, 30 kPa, R134a-likeR410A 20 m riser, 50 kPa

Results

Not enough subcooling: flash gas will form before the expansion valve.

The slope dT_sat/dp at condensing pressure comes from the refrigerant's tables (about 0.03 K/kPa for R134a and 0.02 K/kPa for R410A at 40 °C).

Total pressure loss246.13kPa
Subcooling required4.9227K
Margin-0.92266K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 8 m riser, 30 kPa, R134a-like. The inputs, in the units selected above:

InputValue
Friction and accessory pressure drop30.000 kPa
Vertical lift (liquid rising)8.0000 m
Liquid density1,150.0 kg/m³
Saturation temperature slope, in K per kPa (K/psi ÷ 6.895), from tables0.030000 -
Actual subcooling at condenser outlet5.0000 K

Applying the formula below gives:

ResultValue
Total pressure loss120.22 kPa
Subcooling required3.6066 K
Margin1.3934 K

Open this example in the calculator and change any input.

Formula

\(\Delta p = \Delta p_f + \rho_lgH, \quad \Delta T_{req} = \Delta p\frac{dT_{sat}}{dp}\)

Variables

Symbol Meaning SI unit
\(\Delta p_f\) Friction and accessory pressure drop Pa
\(H\) Vertical lift (liquid rising) m
\(\rho_l\) Liquid density kg/m³
\(dT_{sat}/dp\) Saturation temperature slope (K per kPa, from tables) -
\(\Delta T_{sc}\) Actual subcooling at condenser outlet K
\(\Delta p\) Total pressure loss Pa
\(\Delta T_{req}\) Subcooling required K
\(\Delta T_{sc} - \Delta T_{req}\) Margin K

Method and standards

Static and friction loss against saturation slope.

Where it is used

  • Split systems with condenser below evaporator.
  • Long liquid lines.

Common mistakes

  • Forgetting filter-drier and sight-glass drops.
  • Using vapour density.

Assumptions and limits

  • Linear saturation curve over the drop. The slope is entered in K per kPa in every unit system (a slope in K/psi divided by 6.895).

References

  • ASHRAE Handbook—Refrigeration (2018)
  • ch. 1 (refrigerant piping: liquid lines, subcooling against static and friction losses)

Questions and answers

Why does lift need subcooling?

Liquid rising loses pressure; if its pressure falls below saturation it flashes, starving the expansion valve.

How much subcooling is typical?

3–6 K at the condenser outlet; long risers may need a subcooler.

What do the defaults represent?

An 8 m liquid riser with 30 kPa of friction and fittings, for an R134a-like refrigerant.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.