Worked example
Example: 8 m riser, 30 kPa, R134a-like. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Friction and accessory pressure drop | 30.000 kPa |
| Vertical lift (liquid rising) | 8.0000 m |
| Liquid density | 1,150.0 kg/m³ |
| Saturation temperature slope, in K per kPa (K/psi ÷ 6.895), from tables | 0.030000 - |
| Actual subcooling at condenser outlet | 5.0000 K |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total pressure loss | 120.22 kPa |
| Subcooling required | 3.6066 K |
| Margin | 1.3934 K |
Open this example in the calculator and change any input.
Formula
\(\Delta p = \Delta p_f + \rho_lgH, \quad \Delta T_{req} = \Delta p\frac{dT_{sat}}{dp}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\Delta p_f\) | Friction and accessory pressure drop | Pa |
| \(H\) | Vertical lift (liquid rising) | m |
| \(\rho_l\) | Liquid density | kg/m³ |
| \(dT_{sat}/dp\) | Saturation temperature slope (K per kPa, from tables) | - |
| \(\Delta T_{sc}\) | Actual subcooling at condenser outlet | K |
| \(\Delta p\) | Total pressure loss | Pa |
| \(\Delta T_{req}\) | Subcooling required | K |
| \(\Delta T_{sc} - \Delta T_{req}\) | Margin | K |
Method and standards
Static and friction loss against saturation slope.
Where it is used
- Split systems with condenser below evaporator.
- Long liquid lines.
Common mistakes
- Forgetting filter-drier and sight-glass drops.
- Using vapour density.
Assumptions and limits
- Linear saturation curve over the drop. The slope is entered in K per kPa in every unit system (a slope in K/psi divided by 6.895).
References
- ASHRAE Handbook—Refrigeration (2018)
- ch. 1 (refrigerant piping: liquid lines, subcooling against static and friction losses)
Questions and answers
Why does lift need subcooling?
Liquid rising loses pressure; if its pressure falls below saturation it flashes, starving the expansion valve.
How much subcooling is typical?
3–6 K at the condenser outlet; long risers may need a subcooler.
What do the defaults represent?
An 8 m liquid riser with 30 kPa of friction and fittings, for an R134a-like refrigerant.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.