FireCADCalc

Ice Making: Production from Refrigeration Capacity

Ice production per day from the refrigeration capacity, water and ice temperatures, specific heats and latent heat of fusion, with heat losses allowed.

Food, dairy and textile

Inputs

Examples: 50 TR plant, water 30 °C, ice −5 °CFlake ice 20 TR, 20 °C water, −8 °C

About 333.5 kJ/kg at 0 °C.

Results

Heat removed per kg of ice469.58kJ/kg
Ice production27.501t/d

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 50 TR plant, water 30 °C, ice −5 °C. The inputs, in the units selected above:

InputValue
Refrigeration capacity50.000 TR
Losses (share of capacity)15.000 %
Make-up water temperature30.000 °C
Ice temperature leaving-5.0000 °C
Specific heat of water4.1860 kJ/(kg·K)
Latent heat of fusion of ice333.50 kJ/kg
Specific heat of ice2.1000 kJ/(kg·K)

Applying the formula below gives:

ResultValue
Heat removed per kg of ice469.58 kJ/kg
Ice production27.501 t/d

Open this example in the calculator and change any input.

Formula

\(q = c_w(T_w - 0\,°C) + L + c_i(0\,°C - T_i), \quad \dot m = \frac{\dot Q_e (1 - k_l)}{q}\)

Variables

Symbol Meaning SI unit
\(\dot Q_e\) Refrigeration capacity W
\(k_l\) Losses (share of capacity) -
\(T_w\) Make-up water temperature K
\(T_i\) Ice temperature leaving K
\(c_w\) Specific heat of water J/(kg·K)
\(L\) Latent heat of fusion of ice J/kg
\(c_i\) Specific heat of ice J/(kg·K)
\(q\) Heat removed per kg of ice J/kg
\(\dot m\) Ice production kg/s

Method and standards

Energy balance.

Where it is used

  • Ice plants and fish processing.
  • Concrete cooling with ice.

Common mistakes

  • Ignoring losses.
  • Latent heat only.

Assumptions and limits

  • Steady production.
  • Latent heat default 333.5 kJ/kg (the defrost calculator uses 333.55 kJ/kg, a 0.015 % difference).

References

  • Sensible and latent heat of water and ice

Questions and answers

50 TR, 15 % losses, water at 30 °C, ice at −5 °C?

About 470 kJ per kg: roughly 27.5 t of ice a day.

Why so much less than 'one TR melts a ton a day'?

That old unit uses ice melting at 0 °C; making ice also cools the water and sub-cools the ice.

Losses?

Tank, can and brine losses; your plant's figure.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.