Worked example
Example: R-134a style values. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Refrigerant mass flow | 360.00 kg/h |
| Enthalpy at compressor inlet | 400.00 kJ/kg |
| Enthalpy at compressor outlet | 440.00 kJ/kg |
| Enthalpy at condenser outlet (= evaporator inlet) | 250.00 kJ/kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heating capacity (condenser) | 19.000 kW |
| Cooling capacity (evaporator) | 15.000 kW |
| Compressor power to the refrigerant | 4.0000 kW |
| Heating COP | 4.7500 |
| Cooling COP | 3.7500 |
Open this example in the calculator and change any input.
Formula
\(COP_h = \frac{h_2 - h_3}{h_2 - h_1}, \quad COP_c = \frac{h_1 - h_3}{h_2 - h_1}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m\) | Refrigerant mass flow | kg/s |
| \(h_1\) | Enthalpy at compressor inlet | J/kg |
| \(h_2\) | Enthalpy at compressor outlet | J/kg |
| \(h_3\) | Enthalpy at condenser outlet (= evaporator inlet) | J/kg |
| \(\dot Q_h\) | Heating capacity (condenser) | W |
| \(\dot Q_c\) | Cooling capacity (evaporator) | W |
| \(P\) | Compressor power to the refrigerant | W |
| \(COP_h\) | Heating COP | - |
| \(COP_c\) | Cooling COP | - |
Method and standards
First law.
Where it is used
- Heat pump and chiller checks.
- Refrigeration examinations.
Common mistakes
- Enthalpies from different reference states.
- Mixing kJ and kcal.
Assumptions and limits
- Ideal throttling, steady flow.
References
- First law on the vapour-compression cycle with isenthalpic throttling
Questions and answers
h₁ 400, h₂ 440, h₃ 250 kJ/kg?
Heating COP 4.75, cooling COP 3.75.
Why is heating COP one more than cooling?
The condenser rejects the evaporator heat plus the compressor work.
Where do the enthalpies come from?
Refrigerant tables or a p-h chart at your pressures.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.