Evaporator Defrost Energy, Time and Heat Added to the Room

Heat to melt the frost on an evaporator and warm the coil, the defrost time with a given heater power and efficiency, and the heat left in the cold room.

Process steam and utilitiesDistillery and ethanolChemical and fertiliserFood, dairy and textile

Inputs

Examples: 20 kg frost, 150 kg coil, 12 kWChiller room coil 5 kg, 60 kg, hot gas 70 %

Results

Ice specific heat 2.1 kJ/(kg·K), latent heat of fusion 333.55 kJ/kg; melt water drains away. Only 20–50 % of electric defrost heat reaches the frost; the rest warms the room and coil and returns as refrigeration load.

Useful heat (frost + coil)2.2197MJ
Heat supplied3.1711MJ
Defrost time8.8085min
Heat left in the room and coil (supplied less frost melting)1.4193MJ

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 20 kg frost, 150 kg coil, 12 kW. The inputs, in the units selected above:

InputValue
Frost mass20.000 kg
Coil metal mass150.00 kg
Coil metal specific heat0.70000 kJ/(kg·K)
Coil temperature at start-25.000 °C
Coil temperature at end10.000 °C
Defrost heater power12.000 kW
Defrost efficiency (to frost and coil)40.000 %

Applying the formula below gives:

ResultValue
Useful heat (frost + coil)11.396 MJ
Heat supplied28.490 MJ
Defrost time39.569 min
Heat left in the room and coil (supplied less frost melting)20.769 MJ

Open this example in the calculator and change any input.

Formula

\(E_u = m_f[c_i(0 - t_0) + L_f] + m_cc_c(t_1 - t_0), \quad t_d = \frac{E_u}{\eta_dP_h}\)

Variables

Symbol Meaning SI unit
\(m_f\) Frost mass kg
\(m_c\) Coil metal mass kg
\(c_c\) Coil metal specific heat J/(kg·K)
\(t_0\) Coil temperature at start K
\(t_1\) Coil temperature at end K
\(P_h\) Defrost heater power W
\(\eta_d\) Defrost efficiency (to frost and coil) -
\(E_u\) Useful heat (frost + coil) J
\(E_s\) Heat supplied J
\(t_d\) Defrost time s
\(E_r\) Heat left in the room and coil (supplied less frost melting) J
\(c_i\) Specific heat of ice, fixed at 2 100 J/(kg·K) J/(kg·K)
\(L_f\) Latent heat of fusion of ice, fixed at 333 550 J/kg J/kg

Method and standards

Energy balance.

Where it is used

  • Cold store and freezer load estimates.
  • Defrost heater sizing.

Common mistakes

  • Forgetting the defrost heat in the room load.
  • Over-long defrost cycles.

Assumptions and limits

  • Lumped coil; frost at coil temperature.
  • c_i and L_f are fixed values, not inputs.
  • E_r includes the heat that re-warms the coil; all of it returns as refrigeration load after defrost.

References

  • ASHRAE Handbook—Refrigeration (2018)
  • ch. 14 (forced-circulation air coolers: defrost)

Questions and answers

Why is defrost efficiency so low?

Heaters also warm the air, fins, drain pan and room; hot-gas defrost does better than electric.

How often should coils defrost?

Often enough that frost does not choke the fins: from four times a day to on demand by sensors.

What do the defaults represent?

A freezer-room coil carrying 20 kg of frost with a 12 kW electric defrost.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.