Worked example
Example: 20 kg frost, 150 kg coil, 12 kW. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Frost mass | 20.000 kg |
| Coil metal mass | 150.00 kg |
| Coil metal specific heat | 0.70000 kJ/(kg·K) |
| Coil temperature at start | -25.000 °C |
| Coil temperature at end | 10.000 °C |
| Defrost heater power | 12.000 kW |
| Defrost efficiency (to frost and coil) | 40.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Useful heat (frost + coil) | 11.396 MJ |
| Heat supplied | 28.490 MJ |
| Defrost time | 39.569 min |
| Heat left in the room and coil (supplied less frost melting) | 20.769 MJ |
Open this example in the calculator and change any input.
Formula
\(E_u = m_f[c_i(0 - t_0) + L_f] + m_cc_c(t_1 - t_0), \quad t_d = \frac{E_u}{\eta_dP_h}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(m_f\) | Frost mass | kg |
| \(m_c\) | Coil metal mass | kg |
| \(c_c\) | Coil metal specific heat | J/(kg·K) |
| \(t_0\) | Coil temperature at start | K |
| \(t_1\) | Coil temperature at end | K |
| \(P_h\) | Defrost heater power | W |
| \(\eta_d\) | Defrost efficiency (to frost and coil) | - |
| \(E_u\) | Useful heat (frost + coil) | J |
| \(E_s\) | Heat supplied | J |
| \(t_d\) | Defrost time | s |
| \(E_r\) | Heat left in the room and coil (supplied less frost melting) | J |
| \(c_i\) | Specific heat of ice, fixed at 2 100 J/(kg·K) | J/(kg·K) |
| \(L_f\) | Latent heat of fusion of ice, fixed at 333 550 J/kg | J/kg |
Method and standards
Energy balance.
Where it is used
- Cold store and freezer load estimates.
- Defrost heater sizing.
Common mistakes
- Forgetting the defrost heat in the room load.
- Over-long defrost cycles.
Assumptions and limits
- Lumped coil; frost at coil temperature.
- c_i and L_f are fixed values, not inputs.
- E_r includes the heat that re-warms the coil; all of it returns as refrigeration load after defrost.
References
- ASHRAE Handbook—Refrigeration (2018)
- ch. 14 (forced-circulation air coolers: defrost)
Questions and answers
Why is defrost efficiency so low?
Heaters also warm the air, fins, drain pan and room; hot-gas defrost does better than electric.
How often should coils defrost?
Often enough that frost does not choke the fins: from four times a day to on demand by sensors.
What do the defaults represent?
A freezer-room coil carrying 20 kg of frost with a 12 kW electric defrost.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.