FireCADCalc

Reciprocating Compressor Displacement and Refrigerant Flow

Swept volume of a reciprocating compressor from bore, stroke, cylinders and speed, the refrigerant mass flow for a volumetric efficiency, and the capacity.

Food, dairy and textileRefrigeration and air-conditioning mechanic examinations

Inputs

Examples: 4 × 70/60 mm at 1450 rpmAmmonia 8 × 110/90 mm at 960 rpm

From refrigerant tables at the suction state.

Results

Swept volume394.12m³/h
Actual suction volume295.59m³/h
Refrigerant mass flow703.79kg/h
Refrigerating capacity61.147TR

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 4 × 70/60 mm at 1450 rpm. The inputs, in the units selected above:

InputValue
Bore70.000 mm
Stroke60.000 mm
Number of cylinders4.0000 -
Speed1,450.0 rpm
Volumetric efficiency80.000 %
Suction specific volume0.050000 m³/kg
Refrigerating effect h₁ − h₄150.00 kJ/kg

Applying the formula below gives:

ResultValue
Swept volume80.356 m³/h
Actual suction volume64.285 m³/h
Refrigerant mass flow1,285.7 kg/h
Refrigerating capacity15.232 TR

Open this example in the calculator and change any input.

Formula

\(\dot V_d = \frac{\pi D^2}{4} S z N, \quad \dot m = \frac{\eta_v \dot V_d}{v_1}\)

Variables

Symbol Meaning SI unit
\(D\) Bore m
\(S\) Stroke m
\(z\) Number of cylinders -
\(N\) Speed 1/s
\(\eta_v\) Volumetric efficiency -
\(v_1\) Suction specific volume m³/kg
\(q_e\) Refrigerating effect h₁ − h₄ J/kg
\(\dot V_d\) Swept volume m³/s
\(\dot V_a\) Actual suction volume m³/s
\(\dot m\) Refrigerant mass flow kg/s
\(\dot Q_e\) Refrigerating capacity W

Method and standards

Geometry and continuity.

Where it is used

  • Refrigeration plant checks.
  • Refrigeration examinations.

Common mistakes

  • rpm not converted to per second.
  • Discharge instead of suction volume.

Assumptions and limits

  • Single-acting cylinders.

References

  • Swept volume (π/4)D²S z N; ṁ = η_v V̇_d / v₁

Questions and answers

70 × 60 mm, 4 cylinders at 1450 rpm?

About 80 m³/h swept; with η_v 0.8 and 0.05 m³/kg, 0.36 kg/s, about 15 TR at 150 kJ/kg.

What lowers η_v?

Clearance gas re-expanding, valve losses and suction heating.

Screw compressors?

Use the maker's displacement; the mass flow step is the same.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.