Worked example
Example: 4 × 70/60 mm at 1450 rpm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Bore | 70.000 mm |
| Stroke | 60.000 mm |
| Number of cylinders | 4.0000 - |
| Speed | 1,450.0 rpm |
| Volumetric efficiency | 80.000 % |
| Suction specific volume | 0.050000 m³/kg |
| Refrigerating effect h₁ − h₄ | 150.00 kJ/kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Swept volume | 80.356 m³/h |
| Actual suction volume | 64.285 m³/h |
| Refrigerant mass flow | 1,285.7 kg/h |
| Refrigerating capacity | 15.232 TR |
Open this example in the calculator and change any input.
Formula
\(\dot V_d = \frac{\pi D^2}{4} S z N, \quad \dot m = \frac{\eta_v \dot V_d}{v_1}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D\) | Bore | m |
| \(S\) | Stroke | m |
| \(z\) | Number of cylinders | - |
| \(N\) | Speed | 1/s |
| \(\eta_v\) | Volumetric efficiency | - |
| \(v_1\) | Suction specific volume | m³/kg |
| \(q_e\) | Refrigerating effect h₁ − h₄ | J/kg |
| \(\dot V_d\) | Swept volume | m³/s |
| \(\dot V_a\) | Actual suction volume | m³/s |
| \(\dot m\) | Refrigerant mass flow | kg/s |
| \(\dot Q_e\) | Refrigerating capacity | W |
Method and standards
Geometry and continuity.
Where it is used
- Refrigeration plant checks.
- Refrigeration examinations.
Common mistakes
- rpm not converted to per second.
- Discharge instead of suction volume.
Assumptions and limits
- Single-acting cylinders.
References
- Swept volume (π/4)D²S z N; ṁ = η_v V̇_d / v₁
Questions and answers
70 × 60 mm, 4 cylinders at 1450 rpm?
About 80 m³/h swept; with η_v 0.8 and 0.05 m³/kg, 0.36 kg/s, about 15 TR at 150 kJ/kg.
What lowers η_v?
Clearance gas re-expanding, valve losses and suction heating.
Screw compressors?
Use the maker's displacement; the mass flow step is the same.