Worked example
Example: Freezer door −20 °C to 30 °C, open 10 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Door width | 2.0000 m |
| Door height | 2.5000 m |
| Cold room temperature | -20.000 °C |
| Cold room relative humidity | 85.000 % |
| Warm side temperature | 30.000 °C |
| Warm side relative humidity | 60.000 % |
| Share of time the door is open | 10.000 % |
| Doorway flow factor | 0.80000 - |
| Doorway protection effectiveness | 0 % |
| Barometric pressure (absolute) | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Cold air density | 1.3940 kg/m³ |
| Warm air density | 1.1534 kg/m³ |
| Density factor | 0.95302 |
| Air exchange with the door fully open | 10,871 kg/h |
| Average infiltration load | 21.740 kW |
Open this example in the calculator and change any input.
Formula
\(\dot m = 0.221 A \rho_c F_m \sqrt{\left(1 - \frac{\rho_w}{\rho_c}\right) g H}, \quad F_m = \left[\frac{2}{1 + (\rho_c/\rho_w)^{1/3}}\right]^{1.5}, \quad \dot Q = \dot m (h_w - h_c) D_t F_f (1 - E)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(W_d\) | Door width | m |
| \(H_d\) | Door height | m |
| \(T_c\) | Cold room temperature | K |
| \(\varphi_c\) | Cold room relative humidity | - |
| \(T_w\) | Warm side temperature | K |
| \(\varphi_w\) | Warm side relative humidity | - |
| \(D_t\) | Share of time the door is open | - |
| \(F_f\) | Doorway flow factor | - |
| \(E\) | Doorway protection effectiveness | - |
| \(p\) | Barometric pressure (absolute) | Pa |
| \(\rho_c\) | Cold air density | kg/m³ |
| \(\rho_w\) | Warm air density | kg/m³ |
| \(F_m\) | Density factor | - |
| \(\dot m\) | Air exchange with the door fully open | kg/s |
| \(\dot Q\) | Average infiltration load | W |
Method and standards
Gosney–Olama.
Where it is used
- Cold store and blast freezer loads.
- Justifying air or strip curtains.
Common mistakes
- Using 24 h open time.
- Ignoring frost latent heat.
Assumptions and limits
- Rectangular door, steady exchange while open.
- Door area A = W_d H_d; the mass flow uses the cold-side density ρ_c, as in the cited form.
- Moisture enters as vapour: the latent heat of fusion of the frost it forms on the coil is not included.
References
- Gosney and Olama (1975)
- Heat and enthalpy gains through cold room doorways
- Proc. Inst. Refrig. 72; form as given in the EnergyPlus Engineering Reference (refrigeration door mixing)
Questions and answers
2 × 2.5 m door, −20 °C store, 30 °C outside, open 10 % of the time?
Roughly 22 kW average infiltration load with no protection.
How much does a strip curtain save?
With E 0.9 the load falls to a tenth while the door is open.
Is the formula exact?
Field studies found real flows often lower (correction factors 0.4–0.6 for personnel doors); it is conservative.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.