Cold Store Door Infiltration Load (Gosney–Olama)

Refrigeration load from warm air entering through an open cold store door by the Gosney–Olama relation, with door open time, flow factor and protection.

Food, dairy and textile

Inputs

Examples: Freezer door −20 °C to 30 °C, open 10 %Chill room 2 °C, strip curtain

EnergyPlus uses 0.8 for temperature differences above 11 K and 1.1 below.
0 none; about 0.5 for an air curtain and 0.9 for a strip curtain (EnergyPlus values).

Results

Enthalpies treat moisture as vapour; frost formed on the coil adds the latent heat of fusion on top.

Cold air density1.2799kg/m³
Warm air density1.1770kg/m³
Density factor0.97912
Air exchange with the door fully open4,333.8kg/h
Average infiltration load1.0192kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Freezer door −20 °C to 30 °C, open 10 %. The inputs, in the units selected above:

InputValue
Door width2.0000 m
Door height2.5000 m
Cold room temperature-20.000 °C
Cold room relative humidity85.000 %
Warm side temperature30.000 °C
Warm side relative humidity60.000 %
Share of time the door is open10.000 %
Doorway flow factor0.80000 -
Doorway protection effectiveness0 %
Barometric pressure (absolute)101.33 kPa

Applying the formula below gives:

ResultValue
Cold air density1.3940 kg/m³
Warm air density1.1534 kg/m³
Density factor0.95302
Air exchange with the door fully open10,871 kg/h
Average infiltration load21.740 kW

Open this example in the calculator and change any input.

Formula

\(\dot m = 0.221 A \rho_c F_m \sqrt{\left(1 - \frac{\rho_w}{\rho_c}\right) g H}, \quad F_m = \left[\frac{2}{1 + (\rho_c/\rho_w)^{1/3}}\right]^{1.5}, \quad \dot Q = \dot m (h_w - h_c) D_t F_f (1 - E)\)

Variables

Symbol Meaning SI unit
\(W_d\) Door width m
\(H_d\) Door height m
\(T_c\) Cold room temperature K
\(\varphi_c\) Cold room relative humidity -
\(T_w\) Warm side temperature K
\(\varphi_w\) Warm side relative humidity -
\(D_t\) Share of time the door is open -
\(F_f\) Doorway flow factor -
\(E\) Doorway protection effectiveness -
\(p\) Barometric pressure (absolute) Pa
\(\rho_c\) Cold air density kg/m³
\(\rho_w\) Warm air density kg/m³
\(F_m\) Density factor -
\(\dot m\) Air exchange with the door fully open kg/s
\(\dot Q\) Average infiltration load W

Method and standards

Gosney–Olama.

Where it is used

  • Cold store and blast freezer loads.
  • Justifying air or strip curtains.

Common mistakes

  • Using 24 h open time.
  • Ignoring frost latent heat.

Assumptions and limits

  • Rectangular door, steady exchange while open.
  • Door area A = W_d H_d; the mass flow uses the cold-side density ρ_c, as in the cited form.
  • Moisture enters as vapour: the latent heat of fusion of the frost it forms on the coil is not included.

References

  • Gosney and Olama (1975)
  • Heat and enthalpy gains through cold room doorways
  • Proc. Inst. Refrig. 72; form as given in the EnergyPlus Engineering Reference (refrigeration door mixing)

Questions and answers

2 × 2.5 m door, −20 °C store, 30 °C outside, open 10 % of the time?

Roughly 22 kW average infiltration load with no protection.

How much does a strip curtain save?

With E 0.9 the load falls to a tenth while the door is open.

Is the formula exact?

Field studies found real flows often lower (correction factors 0.4–0.6 for personnel doors); it is conservative.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.