FireCADCalc

Clearance Volumetric Efficiency and Discharge Temperature

Clearance volumetric efficiency of a reciprocating compressor from the clearance ratio, pressure ratio and polytropic index, with the discharge temperature.

Food, dairy and textileRefrigeration and air-conditioning mechanic examinations

Inputs

Examples: 5 %, 2 to 12 barAir compressor 4 %, 1 to 8 bar, n 1.3No clearance

Results

Real volumetric efficiency is lower still (valves, heating, leakage).

Pressure ratio8.0000
Clearance volumetric efficiency84.196%
Discharge temperature (polytropic, ideal gas)216.70°C
Pressure ratio at which η_v falls to zero69.098

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5 %, 2 to 12 bar. The inputs, in the units selected above:

InputValue
Clearance ratio (clearance / swept volume)5.0000 %
Suction pressure (absolute)2.0000 bar
Discharge pressure (absolute)12.000 bar
Polytropic index of re-expansion and compression1.1500 -
Suction temperature-5.0000 °C

Applying the formula below gives:

ResultValue
Pressure ratio6.0000
Clearance volumetric efficiency81.252 %
Discharge temperature (polytropic, ideal gas)65.597 °C
Pressure ratio at which η_v falls to zero33.155

Open this example in the calculator and change any input.

Formula

\(\eta_{v,c} = 1 + c - c\left(\frac{p_2}{p_1}\right)^{1/n}, \quad T_2 = T_1\left(\frac{p_2}{p_1}\right)^{(n-1)/n}\)

Variables

Symbol Meaning SI unit
\(c\) Clearance ratio (clearance / swept volume) -
\(p_1\) Suction pressure (absolute) Pa
\(p_2\) Discharge pressure (absolute) Pa
\(n\) Polytropic index of re-expansion and compression -
\(T_1\) Suction temperature K
\(r\) Pressure ratio -
\(\eta_{v,c}\) Clearance volumetric efficiency -
\(T_2\) Discharge temperature (polytropic, ideal gas) K
\(r_{max}\) Pressure ratio at which η_v falls to zero -

Method and standards

Polytropic re-expansion.

Where it is used

  • Refrigeration and air compressor checks.
  • Examinations.

Common mistakes

  • Gauge pressures.
  • Using η_v,c as the actual efficiency.

Assumptions and limits

  • Polytropic process, ideal gas.
  • With zero clearance the limiting pressure ratio is infinite and is not shown.

References

  • Clearance volumetric efficiency η_v = 1 + c − c(p₂/p₁)^(1/n); polytropic T₂/T₁ = r^((n−1)/n) (thermodynamics texts)

Questions and answers

5 % clearance, 2 to 12 bar, n 1.15?

Pressure ratio 6: η_v about 81 %.

Why does a high ratio hurt?

Clearance gas re-expands over more of the stroke before fresh gas enters.

Discharge temperature?

An ideal-gas estimate; real refrigerants need tables.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.